Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2015860
Status: Active
Facility Name: Liberty Fuel, Inc
Address: 285 N. McLean Boulevard Elgin, IL 60120
County: Kane
Property Parcel: 06-15-251-001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001460
Green Tag Issue Date: 6/13/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: MTB Investments, LLC
Owner Address: 285 N. McLean Blvd. Elgin, IL 60123
Owner Status: Current Owner
Purchase Date: 12/10/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 6/17/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040651 MTB Investments, LLC Current Owner 12/10/2021
U0033137 M.G.& A. Petro Corporation Former Owner 11/10/2005
U0034781 AMM Petro, Inc. Former Owner
U0030136 Newman, Wayne Former Owner
U0016111 WD Oil Co Inc Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260502 (Pending)    Issue Date: 2/26/2026    Expiration Date: 4/27/2026    View NOV Form

Tanks Violations
3 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated, or missing, the cover and supporting components that are defective shall be replaced.
3, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
3, 5 Tank monitor does not appear to function properly and requires maintenance. - ATG in alarm; repair/replace as necessary to secure alarm. Both tanks show loww product and fail 0.2.
3 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump(s) contain(s) liquid, creating alarm on ATG. Remove liquid and repair containment to prevent further liquid ingress. Repair/replace sensor(s) as necessary to clear alarm. ALSO PERMIT TO REMOVE CATHODIC PROTECTION AND MAINTAIN SENSORS.
3 Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - UDC sump 3/4 contains liquid, creating alarm on ATG. Remove liquid and repair containment to prevent further liquid ingress. Repair/replace sensor(s) as necessary to clear alarm. ALSO PERMIT TO REMOVE CATHODIC PROTECTION AND MAINTAIN SENSORS.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline Removed Federal $0.00 04/25/1988 - REM
2 6000 Gasoline Removed Federal $0.00 04/25/1988 - REM
3 4000 Gasoline - Premium Currently in use Federal $0.00
4 500 Used Oil Removed Federal $0.00 04/25/1988 - REM
5 10000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active

MFD Motorfuel Dispensing Forms