Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2015506
Status: Active
Facility Name: Ron Hopkins Ford, Inc.
Address: 1045 East Chicago Street Elgin, IL 60120
County: Kane
Property Parcel:
Facility Type: Auto Dealer
Owner Type: Private
Green Tag Decal: Z003999
Green Tag Issue Date: 5/15/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Fleet

Owner Details

Owner Name: Ron Hopkins Ford, Inc.
Owner Address: 1045 East Chicago Street Elgin, IL 60120
Owner Status: Current Owner
Purchase Date: 5/1/1985
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/26/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0014673 Ron Hopkins Ford, Inc. Current Owner 5/1/1985

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261260 (Pending)    Issue Date: 5/13/2026    Expiration Date: 7/12/2026    View NOV Form

Tanks Violations
Facility A/B operator retraining required as a result of issuance of the Notice of Violation and must be completed within 30 days.
Facility Emergency contact information for A/B & C Operators not posted at unmanned facility
Facility Missing list of designated Class A/B & C Operators - NOT UPDATED OR UTILIZED
6, 7, 8, 9 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
6, 7, 8, 9 Tank monitor does not appear to function properly and requires maintenance. - Indicator POWER/GREEN light on panel of Veeder-Root ATG is not functional. Replace as necessary to provide proper operation.

NOV Number: E0020261261 (Pending)    Issue Date: 5/13/2026    Expiration Date: 7/12/2026    View NOV Form

Tanks Violations
Facility Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters - Provide and install appropriate sign identifying emergency shutoff switch location.
Facility Fire Extinguishers - Minimum 4A:60BC are not present at each island and at an emergency shutoff switch - Provide min of 2 fire extinguishers (4A:60 BC rated), installed to provide access to both employees and customers.
Facility Fire Extinguishers - Past due for annual testing - Fire extinguishers require annual testing. Have annual testing performed and tag all fire extinguishers accordingly. NO TAG ON ONLY FIRE EXTINGUISHER.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
96-1317 7/23/1996 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Diesel Fuel Removed Federal $0.00 11/15/1990 - REM
2 6000 Gasoline Removed Federal $0.00 11/15/1990 - REM
3 1000 Used Oil Removed Federal $0.00 07/23/1996 - REM
4 1000 Automatic Transmission Fluid Removed Federal $0.00 07/23/1996 - REM
5 560 Lube Oil Removed Federal $0.00 07/23/1996 - REM
6 4000 Gasoline - Regular Currently in use Federal $0.00
7 650 Used Oil Currently in use Federal $0.00
8 650 Automatic Transmission Fluid Currently in use Federal $0.00
9 650 New Oil Currently in use Federal $0.00

Dispenser Information

Name\ID Status
REG Active

MFD Motorfuel Dispensing Forms