3, 5, 6 |
Dispensers - hoses cracked, split or worn and require replacement |
3, 5, 6, 7, 8, 9 |
Line interstitial sensors have been raised and rendered inoperational. - Under dispensers 1/2, 3/4, 5/6, 9/10, 11/12 |
7 |
Miscellaneous - When removing sump cover support ring came out with it. Ring needs to be anchored to the concrete. |
3, 5, 6, 7, 8 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
3, 5, 6, 7, 8, 9 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
3, 5, 6 |
Tank monitor does not appear to function properly and requires maintenance. - Alarm light out |
6 |
Tank monitor does not appear to function properly and requires maintenance. - ATG reading shows 1.62" of water, tank tested with stick and water detecting paste resulting in no color change |
7, 8, 9 |
Tank monitor does not appear to function properly and requires maintenance. - Alarm light out |
3 |
Triennial spill prevention equipment testing not completed. |
3, 5, 6, 7, 8, 9 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). |
3, 5, 6, 7, 8, 9 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Dispensers 1/2, 3/4, 5/6, 9/10, 11/12 |