Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2014595
Status: Active
Facility Name: Speedway 7616
Address: 115 N. 8th Street West Dundee, IL 601182013
County: Kane
Property Parcel: 03-22-451-015
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001404
Green Tag Issue Date: 3/19/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Speedway, LLC
Owner Address: P.O. Box 1500 Springfield, OH 45501
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/8/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0026552 Speedway, LLC Current Owner
U0002795 Emro Marketing Co Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00262-2026UPG Upgrade Approved / Issued 3/9/2026 3/9/2026 9/9/2026 Documents
01625-2025UPG Upgrade Approved / Amended 12/5/2025 12/7/2025 6/9/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020261084 (Pending)    Issue Date: 4/22/2026    Expiration Date: 6/21/2026    View NOV Form

Tanks Violations
7 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated, or missing, the cover and supporting components that are defective shall be replaced. SPECIFICALLY THE EAST DIESEL FILL LID IS STUCK IN THE BROKEN CONCRETE WITH SUNKEN IN AND BROKEN CONCRETE. REPAIR METEAL RING/CONCRETE AROUND THE FILL SO THE FILL LID CAN BE OPENED WITHOUT FURTHER DAMAGE.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing copy of written UST facility operation & maintenance plan - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
5, 6, 7, 8 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth. NO LEAK RECORDS FOR JAN-MARCH 2026, I PRINTED APRIL. NO LEAK RECORDS FOR APRIL-DEC OF 2024.
8 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - SPILL BUCKET IS FULL OF WATER OVER THE FILL LID.

NOV Number: E0020261085 (Pending)    Issue Date: 4/22/2026    Expiration Date: 6/21/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
95-2227 Eligible 8/2/1996 9/6/1996 $10,000
95-2227 Eligible 8/29/2003 9/12/2003 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline Removed Federal $0.00 10/26/1995 - REM
2 6000 Gasoline Removed Federal $0.00 10/26/1995 - REM
3 6000 Gasoline Removed Federal $0.00 10/26/1995 - REM
4 6000 Gasoline Removed Federal $0.00 10/26/1995 - REM
5 20000 Gasoline - Regular Currently in use Federal $0.00
6 12000 Gasoline - Premium Currently in use Federal $0.00
7 4000 Diesel Fuel Currently in use Federal $0.00
8 4000 B-11 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms

No Forms Found