Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2014567
Status: Active
Facility Name: Speedway #7505
Address: 1395 Arlington Heights Road Itasca, IL 60143
County: Du Page
Property Parcel: 03-05-201-059
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000190
Green Tag Issue Date: 9/9/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Speedway, LLC
Owner Address: P.O. Box 1500 Springfield, OH 45501
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/8/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0026552 Speedway, LLC Current Owner
U0016241 Emro Marketing Co Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261166 (Pending)    Issue Date: 5/4/2026    Expiration Date: 7/3/2026    View NOV Form

Tanks Violations
1, 2, 3 Miscellaneous - There is a slight leak under dispenser 9/10.
1, 2, 4 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - The ball floats on all three tanks do not have testing dates since 12/20/22. Triannual test is required.
1, 2, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
93-1159 7/22/1993 Removal Log
93-1159 7/23/1993 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
93-1159 Eligible 7/5/1995 7/25/1995 $10,000
06-1069 Eligible 12/8/2006 12/15/2006 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/2/1993 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 7/1/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/18/2024 7/18/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/19/2025 11/19/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/19/2025 11/19/2026
Overfill Prev Device Ball Float Vent Valve OPW 30MV 12/20/2022 12/20/2025
Overfill Prev Device Overfill Drop Tube Valve 11/19/2025 11/19/2028
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/16/2024 5/16/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/2/1993 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 7/1/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/18/2024 7/18/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/19/2025 11/19/2026
Overfill Prev Device Ball Float Vent Valve OPW 30MV 12/20/2022 12/20/2025
Overfill Prev Device Overfill Drop Tube Valve 11/19/2025 11/19/2028
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/16/2024 5/16/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/2/1993 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 7/1/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/18/2024 7/18/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/19/2025 11/19/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/19/2025 11/19/2026
Overfill Prev Device Ball Float Vent Valve OPW 30MV 4/11/2026 4/11/2029
Overfill Prev Device Overfill Drop Tube Valve 4/11/2026 4/11/2029
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/16/2024 5/16/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/2/1993 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 7/1/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/18/2024 7/18/2027
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/19/2025 11/19/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/19/2025 11/19/2026
Overfill Prev Device Ball Float Vent Valve OPW 30MV 12/20/2022 12/20/2025
Overfill Prev Device Overfill Drop Tube Valve 11/19/2025 11/19/2028
Piping Flexible Double Wall A.P.T. Poly Tech S150SC N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/16/2024 5/16/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/22/1993
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 1/1/1969 Red Tag Issue Date:
Last Used Date: 7/1/1993 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/22/1993
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 1/1/1969 Red Tag Issue Date:
Last Used Date: 7/1/1993 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/22/1993
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 1/1/1969 Red Tag Issue Date:
Last Used Date: 7/1/1993 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/23/1993
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 1/1/1978 Red Tag Issue Date:
Last Used Date: 7/1/1993 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 9

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/23/1993
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 1/1/1978 Red Tag Issue Date:
Last Used Date: 7/1/1993 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 10

Capacity: 1000 Petroleum Use:
Product: CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/1/1987
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 1/1/1974 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 11

Capacity: 550 Petroleum Use:
Product: CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/1/1987
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 1/1/1974 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found