Notice of Violatlions (Current)
NOV Number:
E0020261166
(Pending)
Issue Date:
5/4/2026
Expiration Date:
7/3/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3 |
Miscellaneous - There is a slight leak under dispenser 9/10. |
| 1, 2, 4 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - The ball floats on all three tanks do not have testing dates since 12/20/22. Triannual test is required. |
| 1, 2, 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall
be maintained in a dry, clean state. |