7, 8 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP sump covers are cracked and need to be replaced. They may fail with vehicles driving over them. |
7, 8 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose dispenser 6 regular and premium. |
Facility |
Electrical Does Not Comply - Tank 8 regular STP sump has open electric. Replace cap from junction box. |
Facility |
Miscellaneous - Warning signs at dispensers are fading and hard to read. 175.220 a) Minimum signage requires letters shall not be less than 7/8” in height. The top of the sign shall be mounted no higher than 10’ above grade. The wording shall include a minimum of 1) “Warning” 2) “Stop Engine” 3) “No Smoking” 4) “Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress” 5) “It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers” |
9 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - There is liquid in diesel STP sump. Remove liquid. |