Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2013837
Status: Active
Facility Name: Speedway #8440
Address: 701 North Independence Street Romeoville, IL 60446
County: Will
Property Parcel: 12-02-27-311-017-000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001033
Green Tag Issue Date: 9/21/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Speedway, LLC
Owner Address: P.O. Box 1500 Springfield, OH 45501
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/13/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 9/21/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0026552 Speedway, LLC Current Owner
U0002795 Emro Marketing Co Former Owner 2/9/1995
U0009659 Marathon Petroleum Company LP Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251702 (Pending)    Issue Date: 7/8/2025    Expiration Date: 9/6/2025    View NOV Form

Tanks Violations
4, 5, 6, 7 Annual electronic line leak detector test not completed. - Last test was 1/3/2024.
4, 5, 6, 7 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Dispensers 1-10 underground containment sumps last test was 4/17/2021

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
94-1082 Eligible 7/19/1994 8/1/1994 $10,000
95-0631 Eligible 11/14/1996 12/24/1996 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/29/1995
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: 3/1/1995 Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/29/1995
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: 3/1/1995 Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/29/1995
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: 3/1/1995 Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 4000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/25/1995 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 4/1/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/1/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 10/11/2022 10/11/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/29/2025 1/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 1/29/2025 1/29/2026
Overfill Prev Device Overfill Drop Tube Valve 1/4/2023 1/4/2026
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 4/2/2024 4/2/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 5/21/2020 5/21/2021
Leak Detect - Piping Sump Sensor 1/29/2025 1/29/2026
Spill Contain Device Single Wall Spill Bucket 4/2/2024 4/2/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 4000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/25/1995 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 4/1/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/1/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 8/16/2022 8/16/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/29/2025 1/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 1/29/2025 1/29/2026
Overfill Prev Device Overfill Drop Tube Valve 1/4/2023 1/4/2026
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 4/2/2024 4/2/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 5/21/2020 5/21/2021
Leak Detect - Piping Discriminating Sump Sensor 1/13/2022 1/13/2023
Leak Detect - Piping Sump Sensor with positive shutdown 1/29/2025 1/29/2026
Spill Contain Device Single Wall Spill Bucket 4/2/2024 4/2/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/25/1995 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 4/1/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/1/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 8/16/2022 8/16/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/29/2025 1/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 1/29/2025 1/29/2026
Overfill Prev Device Overfill Drop Tube Valve 1/4/2023 1/4/2026
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 4/2/2024 4/2/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 3/9/2020 3/9/2021
Leak Detect - Piping Non-Discriminating Sump Sensor 8/17/2020 8/17/2021
Leak Detect - Piping Discriminating Sump Sensor 1/25/2021 1/25/2022
Leak Detect - Piping Sump Sensor 1/29/2025 1/29/2026
Spill Contain Device Single Wall Spill Bucket 4/2/2024 4/2/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/25/1995 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 4/1/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/1/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 8/16/2022 8/16/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/29/2025 1/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 1/29/2025 1/29/2026
Overfill Prev Device Overfill Drop Tube Valve 1/4/2023 1/4/2026
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 6/3/2024 6/3/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 3/9/2020 3/9/2021
Leak Detect - Piping Discriminating Sump Sensor 1/25/2021 1/13/2022
Leak Detect - Piping Sump Sensor 1/29/2025 1/29/2026
Spill Contain Device Single Wall Spill Bucket 4/2/2024 4/2/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/2/2024 4/2/2027
Leak Detect - Piping Sump Sensor 1/29/2025 1/29/2026



Name\ID 11

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/2/2024 4/2/2027
Leak Detect - Piping Sump Sensor 1/29/2025 1/29/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/2/2024 4/2/2027
Leak Detect - Piping Sump Sensor 1/29/2025 1/29/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/2/2024 4/2/2027
Leak Detect - Piping Sump Sensor 1/29/2025 1/29/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/2/2024 4/2/2027
Leak Detect - Piping Sump Sensor 1/29/2025 1/29/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/2/2024 4/2/2027
Leak Detect - Piping Sump Sensor 1/29/2025 1/29/2026

MFD Motorfuel Dispensing Forms