Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2013808
Status: Active
Facility Name: T & S Mobile, Inc.
Address: 1144 E. 162nd Street South Holland, IL 60473
County: Cook
Property Parcel: 29-14-317-025-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002910
Green Tag Issue Date: 10/16/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: SAT Enterprises, Inc.
Owner Address: 133 Singletree Road Orland Park, IL 60467
Owner Status: Current Owner / Operator
Purchase Date: 4/29/2009
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 12/14/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/16/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035943 SAT Enterprises, Inc. Current Owner / Operator 4/29/2009
U0026531 DO NOT USE THIS OWNER ID - Casey's General Stores Former Owner
U0035847 T & S Marathon, Former Owner / Operator 4/30/2009
U0035252 MPCO Real Estate, LLC Former Owner / Operator 1/23/2009
U0009659 Marathon Petroleum Company LP Former Owner / Operator 12/31/1967

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00587-2025UPG Upgrade Approved / Issued 5/13/2025 5/13/2025 11/13/2025 Documents

Notice of Violatlions (Current)

NOV Number: E0020251460 (Pending)    Issue Date: 6/6/2025    Expiration Date: 8/5/2025    View NOV Form

Tanks Violations
12, 16 Install or replace lockable fill pipe caps. - E-85 and Premium Snap cap is broke. Repair/Replace
Facility Missing copies of 30 day Walkthrough Inspection Report. - Needs to be filled out correctly.
Facility Missing list of designated Class A/B & C Operators - List of A/B/C Operators- can be found at https://sfm.illinois.gov/content/dam/soi/en/web/sfm/sfmdocuments/documents/listofdesignatedoperators.pdf
10 Open electrical conduit or junction boxes. - ATG Junction box is missing the cap. Replace cap to junction box. (Regular ATG)
10, 15, 16 Piping interstitial must be open in all sumps - Product piping test boots shall be pulled back after testing to allow the interstice to be open to the sump sensors 175.420 b) (Or Shrader valves need to be removed) (STPS.)
15, 16 Required monthly tank interstitial sensor records not available. - Monthly passing tapes. (2 wire CL Status)
10, 11, 12 Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Dispenser 5/6

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
10-0595 Returned 7/16/2010 8/25/2010 $Not Selected
10-0595 Returned 8/30/2010 10/18/2010 $Not Selected
10-0595 Eligible 10/27/2010 12/16/2010 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
6 4000 Gasoline Removed Federal $0.00 09/12/1988 - REM
7 4000 Gasoline Removed Federal $0.00 09/12/1988 - REM
8 4000 Gasoline Removed Federal $0.00 09/12/1988 - REM
9 4000 Gasoline Removed Federal $0.00 09/12/1988 - REM
10 10000 Gasoline - Regular Currently in use Federal $0.00
11 10000 Gasoline - Regular Currently in use Federal $0.00
12 10000 Gasoline - Premium Currently in use Federal $0.00
13 550 Used Oil Removed Federal $0.00 12/24/1997 - REM
14 550 Used Oil Removed Federal $0.00 09/12/1988 - REM
15 5000 Diesel Fuel Currently in use Federal $0.00
16 5000 E85 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
9/10 Active
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms