Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2013065
Status: Active
Facility Name: JCBK BP Gas Mart, Inc.
Address: 3057 N. Kedzie Avenue Chicago, IL 60618
County: Cook
Property Parcel: 13-25-112-001-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z002370
Green Tag Issue Date: 3/12/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: JCBK BP Gas Mart, Inc.
Owner Address: 3057 N. Kedzie Ave. Chicago, IL 60618
Owner Status: Current Owner
Purchase Date: 12/29/2020
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/22/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040561 JCBK BP Gas Mart, Inc. Current Owner 12/29/2020
U0032751 Phil's Enterprises, L.L.C. Former Owner 8/10/2004
U0038959 The Filiberto Quiles Sr. Family Limited Partnership Former Owner 12/18/2002
U0011857 Filiberto Quiles, Former Owner 1/1/1985

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260600 (Pending)    Issue Date: 3/9/2026    Expiration Date: 5/8/2026    View NOV Form

Tanks Violations
3 Line interstitial sensors have been raised and rendered inoperational. - Not correctly installed sensor is laying on its side
Facility Missing copies of 30 day Walkthrough Inspection Report. - https://www2.illinois.gov/sites/sfm/About/Divisions/Petroleum-Chemical-Safety/Pages/Applications-and-Forms.aspx
Facility Missing copies of current testing certificates for operator training - All 3 shifts need to have a certificate for the person operating the station.
2, 3 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - The Premium and Regular (South) tank sumps are filled with water. Excess soil and debris around the sump collars are preventing the lids from fully seating, causing them to remain elevated and allowing water to enter the sumps by gravity. The accumulated material also sits too high to allow proper drainage or absorption into the surrounding ground. Recommended Action: Remove the excess dirt and debris so the sump lids can sit flush on the sump structure and to restore proper grade for drainage and soil absorption.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
03-0433 5/8/2003 Removal Log 107358

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-0433 Eligible 4/23/2004 4/26/2004 $15,000
20030433 Eligible 1/2/2018 1/2/2018 $15,000 Letter
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 3000 Gasoline - Regular Currently in use Federal $0.00
2 3000 Gasoline - Premium Currently in use Federal $0.00
3 5000 Gasoline - Regular Currently in use Federal $0.00
4 550 Gasoline Removed Federal $0.00 05/08/2003 - REM
5 1000 Gasoline Removed Federal $0.00 05/08/2003 - REM
6 1000 Gasoline Removed Federal $0.00 05/08/2003 - REM
7 1000 Used Oil Removed Federal $0.00 05/08/2003 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms