Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2012961
Status: Inactive
Facility Name: Skokie Quik Shop
Address: 5343 West Touhy Avenue Skokie, IL 60077
County: Cook
Property Parcel: 10-33-101-011-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000823
Green Tag Issue Date: 10/2/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Graham Enterprise, Inc.
Owner Address: 750 Bunker Court Vernon Hills, IL 60061
Owner Status: Current Owner
Purchase Date: 1/15/1993
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/1/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/2/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0023084 Graham Enterprise, Inc. Current Owner 1/15/1993
U0025852 Graham Eugene W Former Owner 5/22/1997
U0006038 Graham C-Stores Company Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00958-2025REM Removal Approved / Issued 7/24/2025 7/24/2025 1/26/2026 Documents
00970-2025INS Install Approved / Issued 7/24/2025 7/28/2025 1/28/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020251420 (Referred to Legal)    Issue Date: 6/3/2025    Expiration Date: 8/2/2025    View NOV Form

Tanks Violations
1, 2, 3 Remove tank(s) - Failed Internal Inspection - Internal lining inspection failed on 4/1/2025. No permit to install a self structural tank has been approved within 60 days of a failed internal lining inspection. Tank(s) are required to be decommissioned. (Per 41 Ill. Adm. Code 175.500(a))

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
92-0289 3/20/1995 Removal Log 2705-94

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
20200154 Eligible 6/24/2020 6/25/2020 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 4/1/1985 Red Tag Issue Date: 4/2/2025
Last Used Date: 4/2/2025 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 6/26/2024 6/26/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/26/2024 6/26/2027
Corrosion Prot - Tank Impressed Current Cathodic Protection 6/26/2024 6/26/2025
Corrosion Prot - Tank Lining Materials Internal 1/21/2020 1/21/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/26/2024 6/26/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 6/26/2024 6/26/2025
Overfill Prev Device Overfill Drop Tube Valve 5/11/2022 5/11/2025
Piping Flex Connector Steel N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/11/2022 5/11/2025
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Fail 11/29/2019
Piping Fiberglass Single Wall Piping A.O. Smith Precision Test (Piping) Pass 12/4/2019
Piping Fiberglass Single Wall Piping A.O. Smith Precision Test (Piping) Pass 2/17/2020
Piping Steel Single Wall Piping Precision Test (Piping) Pass 6/26/2024
Tank Steel Single Wall Precision Test (Tank) Pass 1/22/2020



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 4/1/1985 Red Tag Issue Date: 4/2/2025
Last Used Date: 4/1/2025 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 6/26/2024 6/26/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/26/2024 6/26/2027
Corrosion Prot - Tank Impressed Current Cathodic Protection 6/26/2024 6/26/2025
Corrosion Prot - Tank Lining Materials Internal 1/21/2020 1/21/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/26/2024 6/26/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 6/26/2024 6/26/2025
Overfill Prev Device Overfill Drop Tube Valve 5/5/2022 5/5/2025
Piping Flex Connector Steel N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/5/2022 5/5/2025
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 6/5/2019
Piping Fiberglass Single Wall Piping A.O. Smith Precision Test (Piping) Pass 12/4/2019
Piping Fiberglass Single Wall Piping A.O. Smith Precision Test (Piping) Pass 2/17/2020
Piping Steel Single Wall Piping Precision Test (Piping) Pass 6/26/2024
Tank Steel Single Wall Precision Test (Tank) Pass 1/22/2020



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 4/1/1985 Red Tag Issue Date: 4/2/2025
Last Used Date: 4/1/2025 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 6/26/2024 6/26/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/26/2024 6/26/2027
Corrosion Prot - Tank Impressed Current Cathodic Protection 6/26/2024 6/26/2025
Corrosion Prot - Tank Lining Materials Internal 1/21/2020 1/21/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/26/2024 6/26/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 6/26/2024 6/26/2025
Overfill Prev Device Overfill Drop Tube Valve 5/5/2022 5/5/2025
Piping Flex Connector Steel N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/5/2022 5/5/2025
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 6/5/2019
Piping Steel Single Wall Piping Precision Test (Piping) Pass 6/26/2024
Tank Steel Single Wall Precision Test (Tank) Pass 1/22/2020



Tank Number 4

Capacity: 1000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Pre 1974 CAS Code:
Regulated Status: Exempt Removed Date:
OSFM First Notify Date: 11/16/1994 Abandoned Material:
Current Age: 75 Abandoned Date:
Install Date: 1/1/1950 Red Tag Issue Date:
Last Used Date: 1/1/1971 Fee Due:
Product Date: 1/1/1950

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 550 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Pre 1974 CAS Code:
Regulated Status: Exempt Removed Date:
OSFM First Notify Date: 1/1/1902 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/1/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Not Installed CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Not Installed CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 6000 Petroleum Use:
Product: E15 CERCLA Substance:
Status: Not Installed CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2012961 Skokie Quik Shop Skokie 07/24/2025 Letter Form