Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2011536
Status: Active
Facility Name: Cross America - IL0094
Address: 800 S. Plum Grove Road Palatine, IL 60067
County: Cook
Property Parcel: 02-27-200-032-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000098
Green Tag Issue Date: 7/24/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Lehigh Gas Wholesale Services Inc.
Owner Address: 645 Hamilton, Suite 400 Allentown, PA 18101
Owner Status: Current Owner
Purchase Date: 9/27/2016
Type of Financial Responsibility: Surety Bond
Financial Responsibility Reporting Due Date: 4/14/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037337 Lehigh Gas Wholesale Services Inc. Current Owner 9/27/2016
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 10/23/2014
U0033534 2GR Enterprise, Inc. Former Owner 5/1/2006
U0031549 Himaxi Enterprise, Inc., Former Owner 9/1/2003
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 9/23/1993
U0024983 Clark Refining & Marketing, Inc. Former Owner 5/1/1989
U0000759 Hellstrom Automotive Former Owner 12/31/1967
U0025164 BAPA, LLC & PT, LLC Former Owner
U0029789 Clark Retail Enterprises, Inc. Former Owner
U0028787 Clark Retail Enterprises, Inc., Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00114-2026UPG Upgrade Approved / Issued 1/29/2026 1/29/2026 7/29/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020261323 (Pending)    Issue Date: 5/19/2026    Expiration Date: 7/18/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
6 Annual leak detection certification not completed (Required annually).
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
6, 7, 8 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
6, 7, 8 Tank monitor does not appear to function properly and requires maintenance. - Green and Red indicator lights are out and need to be replaced.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/1/1989
OSFM First Notify Date: 3/5/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/1/1989
OSFM First Notify Date: 3/5/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/1/1989
OSFM First Notify Date: 3/5/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/1/1989
OSFM First Notify Date: 3/5/1986 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 4000 Petroleum Use:
Product: CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/1/1989
OSFM First Notify Date: 3/9/1990 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/26/1990 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 1/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 9/25/2025 9/25/2026
Corrosion Prot - Piping Sacrificial Anode Flex Connector 9/25/2025 9/25/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/22/2026 4/22/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/8/2025 4/22/2026
Overfill Prev Device Overfill Drop Tube Valve 5/30/2024 5/30/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/22/2024 5/22/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 4/22/2026
Piping Steel Single Wall Piping Precision Test (Piping) Pass 4/22/2026



Tank Number 7

Capacity: 12000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/26/1990 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 1/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 9/25/2025 9/25/2026
Corrosion Prot - Piping Sacrificial Anode Flex Connector 9/25/2025 9/25/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/22/2026 4/22/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/22/2026 4/22/2027
Overfill Prev Device Overfill Drop Tube Valve 5/22/2024 5/22/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/22/2024 5/22/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/31/2023
Piping Steel Single Wall Piping Precision Test (Piping) Pass 4/22/2026



Tank Number 8

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/26/1990 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 1/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 9/25/2025 9/25/2026
Corrosion Prot - Piping Sacrificial Anode Flex Connector 9/25/2025 9/25/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/22/2026 4/22/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/22/2026 4/22/2027
Overfill Prev Device Overfill Drop Tube Valve 5/22/2024 5/22/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Double Wall Spill Bucket 5/22/2024 5/22/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/31/2023
Piping Steel Single Wall Piping Precision Test (Piping) Pass 4/22/2026

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found