Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0014207 |
7-Eleven, Inc. |
Current Owner |
3/24/2011 |
| U0010471 |
ExxonMobil Oil Corporation |
Former Owner |
6/19/2003 |
| U0007425 |
Illinois State Toll Highway Authority |
Former Owner |
12/1/1985 |
Notice of Violations (Current)
NOV Number:
E0020261522
(Pending)
Issue Date:
6/12/2026
Expiration Date:
8/11/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Miscellaneous - Emergency Stop signage required at diesel island
Emergency stop shall be readily accessible and conspicuously marked by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. (Per 41 Ill Admin code 175.210(d)(3)) |
| 2587 |
Open electrical conduit or junction boxes. - Premium interstitial tank sensor riser is damaged. |
| 2585, 2586, 2587 |
Spill prevention equipment failed triennial testing. Must be repaired or replaced. |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 03-0822 |
6/4/2003 |
Removal Log |
02636-2003REM |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 94-1813 |
Eligible |
12/12/2000
|
12/28/2000
|
$15,000
|
|
| 03-0822 |
Eligible |
2/2/2007
|
3/1/2007
|
$10,000
|
|
Tank Number 1
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
17 |
|
Abandoned Date: |
4/1/1976 |
| Install Date: |
1/1/1968 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
4/1/1976 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
17 |
|
Abandoned Date: |
4/1/1976 |
| Install Date: |
1/1/1968 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
17 |
|
Abandoned Date: |
4/1/1976 |
| Install Date: |
1/1/1968 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
17 |
|
Abandoned Date: |
4/1/1976 |
| Install Date: |
1/1/1968 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
17 |
|
Abandoned Date: |
4/1/1976 |
| Install Date: |
1/1/1968 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
17 |
|
Abandoned Date: |
4/1/1976 |
| Install Date: |
1/1/1968 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 7
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1976 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 8
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1976 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 9
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1976 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 10
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1976 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 11
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1976 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 12
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
12/1/1985 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1976 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
12/1/1985 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 13
| Capacity: |
10000 |
|
Petroleum Use: |
Consumptive Use on Premises for Heating |
| Product: |
Heating Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
State |
|
Removed Date: |
11/9/1989 |
|
OSFM
First Notify Date: |
12/1/1989 |
|
Abandoned Material: |
|
| Current Age: |
31 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1958 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1974 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 19
| Capacity: |
500 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
1/1/1989 |
|
OSFM
First Notify Date: |
9/28/1995 |
|
Abandoned Material: |
|
| Current Age: |
31 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1958 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1974 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 20
| Capacity: |
1000 |
|
Petroleum Use: |
Consumptive Use on Premises for Heating |
| Product: |
Heating Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
State |
|
Removed Date: |
1/1/1989 |
|
OSFM
First Notify Date: |
9/28/1995 |
|
Abandoned Material: |
|
| Current Age: |
31 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1958 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1974 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2575
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/4/2003 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
17 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
5/27/2003 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2580
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/4/2003 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
17 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
5/27/2003 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Pressurized Line Leak Detection |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Automatic Tank Gauging |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Steel Single Wall Piping |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Manhole Field Constructed |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 2582
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/4/2003 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
17 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
5/27/2003 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2583
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/4/2003 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
17 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
5/27/2003 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2584
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/4/2003 |
|
OSFM
First Notify Date: |
4/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
17 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
5/27/2003 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2585
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
10/1/2003 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
6/20/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
9/23/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
5/6/2026 |
5/6/2027 |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor |
5/6/2026 |
5/6/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/6/2026 |
5/6/2029 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
2/13/2024 |
2/13/2027 |
Leak Detect - Piping
|
Sump Sensor |
2/13/2024 |
2/13/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
6/7/2023 |
5/6/2026 |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 2586
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
10/1/2003 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
6/20/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
9/23/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Other Non-vented check valve |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor |
5/6/2026 |
5/6/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/6/2026 |
5/6/2029 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
2/13/2024 |
2/13/2027 |
Leak Detect - Piping
|
Sump Sensor |
2/13/2024 |
2/13/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
6/7/2023 |
5/6/2026 |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 2587
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
10/1/2003 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
6/20/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
9/23/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
5/6/2026 |
5/6/2027 |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor |
5/6/2026 |
5/6/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/6/2026 |
5/6/2029 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
2/13/2024 |
2/13/2027 |
Leak Detect - Piping
|
Sump Sensor |
2/13/2024 |
2/13/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
6/7/2023 |
5/6/2026 |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions
|
Precision Test (Tank)
|
Pass
|
9/23/2019
|
Tank Number 2588
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
10/1/2003 |
|
Abandoned Material: |
|
| Current Age: |
22 |
|
Abandoned Date: |
|
| Install Date: |
6/20/2003 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
9/23/2003 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
5/6/2026 |
5/6/2027 |
|
Leak Detect - Tank
|
Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor |
5/6/2026 |
5/6/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
5/6/2026 |
5/6/2029 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
2/13/2024 |
2/13/2027 |
Leak Detect - Piping
|
Sump Sensor |
2/13/2024 |
2/13/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
5/6/2026 |
5/6/2029 |
|
Tank
|
Fiberglass Brine Filled Double Wall Containment Solutions |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall Environ Geo Flex
|
Precision Test (Piping)
|
Pass
|
12/27/2022
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found