Notice of Violatlions (Current)
NOV Number:
E0020260443
(Pending)
Issue Date:
2/24/2026
Expiration Date:
4/25/2026
View NOV Form
| Tanks |
Violations |
| 2003 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Unleaded most South tank must have a new support ring installed for the tank monitor probe containment.
Containments shall have a factory manufactured protective cover and supporting components that are properly maintained. Reference 175.410 a) |
| 2006 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP Cover for the Diesel needs a new cover. Spoke with contractor and it has already been ordered
Containments shall have a factory manufactured protective cover and supporting components that are properly maintained. Reference 175.410 a) |
| 2003, 2004, 2005, 2006 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
NOV Number:
E0020260444
(Pending)
Issue Date:
2/24/2026
Expiration Date:
4/25/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Had been removed, previously had been here in the past |