Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2010110
Status: Active
Facility Name: Oak Forest Go Lo
Address: 15100 S. Cicero Ave. Oak Forest, IL 60452
County: Cook
Property Parcel: 28-16-215-068-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002022
Green Tag Issue Date: 3/12/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Wali Management d/b/a Amstar
Owner Address: 15100 Cicero Ave. Oak Forest, IL 60452
Owner Status: Current Owner
Purchase Date: 8/20/2013
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/1/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/12/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037013 Wali Management d/b/a Amstar Current Owner 8/20/2013
U0036286 Alaa Salman / Noor Oak Forest Former Owner 5/1/2011
U0034726 Mavi Oil, Inc. Former Owner 3/17/2007
U0033270 Muaref, Muaref Former Owner 4/1/2005
U0031397 Oak Forest Food Mart & Gas Former Owner 5/27/2003
U0003073 Clark Retail Enterprises, Inc. Former Owner 11/22/1988
U0003450 Corsi Clara Former Owner 12/31/1967
U0029789 Clark Retail Enterprises, Inc. Former Owner
U0028787 Clark Retail Enterprises, Inc., Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251669 (Pending)    Issue Date: 7/2/2025    Expiration Date: 8/31/2025    View NOV Form

Tanks Violations
1, 2, 3 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
1, 2, 3 Annual leak detection certification not completed (Required annually). - (ATG Cert.)
1, 2, 3 Annual tank impressed current system test not completed.
Facility Facility Operation and Maintenance Plan not completed or available. - Need to completely fill the paper work out. Not complete.
1, 2, 3 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - (Dispensers)
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
Facility Missing list of designated Class A/B & C Operators - Form can be found at https://sfm.illinois.gov to download and complete.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3 Tank monitor does not appear to function properly and requires maintenance. - Indicator light(s) on panel of Veeder-Root ATG is/are not functional. Replace as necessary to provide proper operation. (Green)
2, 3 Triennial spill prevention equipment testing not completed.

NOV Number: E0020251670 (Pending)    Issue Date: 7/2/2025    Expiration Date: 8/31/2025    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020251671 (Pending)    Issue Date: 7/2/2025    Expiration Date: 8/31/2025    View NOV Form

Tanks Violations
Facility Submit Notification Form For Ownership Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. Select “New Owner” as the type of notification form.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline - Regular Currently in use Federal $0.00
2 6000 Gasoline - Regular Currently in use Federal $0.00
3 10000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms

No Forms Found