Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2010066
Status: Active
Facility Name: Friendly Freeport, Inc.,
Address: 2107 W. Grand Ave. Waukegan, IL 60085
County: Lake
Property Parcel: 08-20-103-001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000753
Green Tag Issue Date: 4/11/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Friendly Freeport, Inc.
Owner Address: 6480 Riverside Loves Park, IL 61108
Owner Status: Current Owner
Purchase Date: 9/30/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/2/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/11/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040366 Friendly Freeport, Inc. Current Owner 9/30/2021
U0037337 Lehigh Gas Wholesale Services Inc. Former Owner 9/27/2016
U0025164 BAPA, LLC & PT, LLC Former Owner 4/30/2009
U0034322 Grand Avenue Oil, LLC Former Owner 8/13/2007
U0031215 Classic Oil Company Former Owner 3/12/2003
U0003073 Clark Retail Enterprises, Inc. Former Owner 11/22/1988
U0029789 Clark Retail Enterprises, Inc. Former Owner
U0028787 Clark Retail Enterprises, Inc., Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260075 (Pending)    Issue Date: 1/12/2026    Expiration Date: 3/13/2026    View NOV Form

Tanks Violations
1, 2 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Annual leak detection certification not completed (Required annually).
Facility Facility Operation and Maintenance Plan not completed or available. - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
1, 2 Miscellaneous - Monthly line leak testing records not available.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
1, 2 Precision line test required. - Precision line test is required (Per 41 Ill Admin code 175.640(a)(4))
1, 2 Required monthly tank leak test records not available. - Maintain one NORMAL/PASS report per TANK, per month, from tank monitor. (CSLD)
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
Facility Submit Notification Form For Ownership Change - Submit OSFM Notification Form showing change in facility ownership, complete and submit the online Notification for Underground Storage Tanks form which can be found at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm
1, 2 Tank precision test required. - Precision tank test is required due to missing or failed monthly monitoring (Per 41 Ill Admin code 175.630(c)(2))

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00
3 10000 Gasoline Removed Federal 01/01/1988 - REM
4 7500 Gasoline Removed Federal 01/01/1988 - REM

Dispenser Information

Name\ID Status
1/2 Active
11/12 Active
13/14 Active
15/16 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2010066 Friendly Freeport, Inc., Waukegan 02/23/2017 Letter Form