Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0031495 |
American Petroleum & Gas, Inc. |
Current Owner / Operator |
4/1/2011 |
| U0029789 |
Clark Retail Enterprises, Inc. |
Former Owner |
11/22/1988 |
| U0028787 |
Clark Retail Enterprises, Inc., |
Former Owner |
|
| U0003073 |
Clark Retail Enterprises, Inc. |
Former Owner |
|
| U0032657 |
APC Investment Corporation |
Former Owner / Operator |
1/1/2005 |
| U0031495 |
American Petroleum & Gas, Inc. |
Former Owner / Operator |
8/27/2003 |
Notice of Violations (Current)
NOV Number:
E0020252649
(Referred to Legal)
Issue Date:
10/8/2025
Expiration Date:
12/7/2025
View NOV Form
| Tanks |
Violations |
| 4, 5 |
Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. Upon inspection of these tanks it appears that both still have more than one inch of product remaining in them. |
| Facility |
Financial responsibility must be reported yearly - Per 41 Ill. Adm. Code 176.220, tank owners/operators must submit an electronic Financial Responsibility Report form on an annual basis. The last report submitted, expired on 1/22/11. Financial Responsibility must be maintained until the tanks are removed or properly abandoned in place (if eligible), by a licensed UST decommissioning contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
| 4, 5 |
Submit Notification Form For Tank Status Change - Per 175.810(a)(3), tanks taken out of service are required to notify the OSFM within 30 days of date of last use, on an electronic Notification for Underground Storage Tank form, declaring a tank status change. These two tanks were taken out of service in 2013. Here is the link to the electronic Notification for Underground Storage Tank form, so that you can file that change: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 98-157 |
6/30/1998 |
Removal Log |
1502-98 |
| 98-1578 |
6/30/1998 |
Removal Log |
1502-98 |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 94-0563 |
Eligible |
9/27/1996
|
10/21/1996
|
$10,000
|
|
Tank Number 1
| Capacity: |
7500 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/30/1998 |
|
OSFM
First Notify Date: |
5/2/1986 |
|
Abandoned Material: |
|
| Current Age: |
27 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
7500 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/30/1998 |
|
OSFM
First Notify Date: |
5/2/1986 |
|
Abandoned Material: |
|
| Current Age: |
27 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
7500 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/30/1998 |
|
OSFM
First Notify Date: |
5/2/1986 |
|
Abandoned Material: |
|
| Current Age: |
27 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/3/1999 |
|
Abandoned Material: |
|
| Current Age: |
28 |
|
Abandoned Date: |
|
| Install Date: |
7/2/1998 |
|
Red Tag Issue Date: |
6/27/2013 |
| Last Used Date: |
1/1/2013 |
|
Fee Due: |
$0.00 |
| Product Date: |
7/2/1998 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
11/29/2011 |
11/29/2014 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
11/29/2011 |
11/29/2012 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Red Jacket Pro Max with CSLD |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
11/29/2011 |
11/29/2012 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/3/1998 |
|
Abandoned Material: |
|
| Current Age: |
28 |
|
Abandoned Date: |
|
| Install Date: |
7/2/1998 |
|
Red Tag Issue Date: |
6/27/2013 |
| Last Used Date: |
1/1/2013 |
|
Fee Due: |
$0.00 |
| Product Date: |
7/2/1998 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
11/29/2011 |
11/29/2014 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
11/29/2011 |
11/29/2012 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Red Jacket Pro Max with CSLD |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
11/29/2011 |
11/29/2012 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Double Wall Ameron Dualoy 3000/LCX |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found