Notice of Violatlions (Current)
NOV Number:
E0020260092
(Pending)
Issue Date:
1/13/2026
Expiration Date:
3/14/2026
View NOV Form
| Tanks |
Violations |
| 16 |
Overfill prevention equipment does not appear to function properly. - Float in fill drop tube is not retracting properly, can't stick fuel in tank |
| 16 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 16 |
Tank precision test required. - Tank has 28 gallons of water - have water removed and test tank |