Notice of Violatlions (Current)
NOV Number:
E0020261286
(Pending)
Issue Date:
5/15/2026
Expiration Date:
7/14/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
NOV Number:
E0020261287
(Pending)
Issue Date:
5/15/2026
Expiration Date:
7/14/2026
View NOV Form
| Tanks |
Violations |
| 5 |
Open electrical conduit or junction boxes. - Conduit is broken in regular probe or tank sensor well. Repair so all electric is closed. |
| 6 |
Spill prevention equipment failed triennial testing. Must be repaired or replaced. - Tanknology failed spill bucket on 5/7/26 due to water in interstice. |
| 6 |
Tank interstitial sensors in alarm or failed test, must repair or replace. - Tanknology failed sensor on 5/7/26 due to water in sump. |