Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0040626 |
2380 River Real Estate |
Current Owner |
9/10/2021 |
| U0036617 |
2380 Mobile, LLC |
Former Owner |
8/3/2012 |
| U0036899 |
R and T, Inc. |
Former Owner |
6/1/2012 |
| U0036617 |
2380 Mobile, LLC |
Former Owner |
1/1/2012 |
| U0036013 |
Buchanan Energy (N), LLC |
Former Owner |
12/9/2010 |
| U0010471 |
ExxonMobil Oil Corporation |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020262105
(Pending)
Issue Date:
8/19/2026
Expiration Date:
10/18/2026
View NOV Form
| Tanks |
Violations |
| 4, 5 |
Dispensers - hoses cracked, split or worn and require replacement |
| 6 |
Miscellaneous - ATG to be operated and maintained in accordance with the
manufacturer's instructions. 175.610.a.2 |
| 4, 5, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
NOV Number:
E0020262107
(Pending)
Issue Date:
8/19/2026
Expiration Date:
10/18/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Signs - Dispensers not marked or labeled with the name of product - #6 dispenser |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 91-1316 |
Returned |
8/10/1999
|
8/23/1999
|
$Not Selected
|
|
| 96-0391 |
Eligible |
2/28/2002
|
3/11/2002
|
$15,000
|
|
| 10-0023 |
Eligible |
8/26/2010
|
10/12/2010
|
$15,000
|
|
| 10-0023 |
Eligible |
6/23/2011
|
8/22/2011
|
$15,000
|
|
Tank Number 1
| Capacity: |
1000 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
1/1/1986 |
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
7 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1979 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1986 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
1/1/1986 |
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
23 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1963 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1986 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
1/1/1986 |
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
23 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1963 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1986 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
10/20/1988 |
|
Abandoned Material: |
|
| Current Age: |
40 |
|
Abandoned Date: |
|
| Install Date: |
3/17/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
7/1/2026 |
7/1/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
7/1/2026 |
7/1/2027 |
|
Overfill Prev Device
|
Ball Only Removed Ball Float Vent Valve |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/21/2025 |
7/21/2028 |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated |
7/21/2025 |
7/21/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
7/21/2025 |
7/21/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall
|
Precision Test (Piping)
|
Pass
|
1/9/2023
|
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
7/1/2026
|
Tank Number 5
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
10/20/1988 |
|
Abandoned Material: |
|
| Current Age: |
40 |
|
Abandoned Date: |
|
| Install Date: |
3/17/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
7/1/2026 |
7/1/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
7/1/2026 |
7/1/2027 |
|
Overfill Prev Device
|
Ball Only Removed Ball Float Vent Valve |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/21/2025 |
7/21/2028 |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated |
7/21/2025 |
7/21/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
8/28/2025 |
8/28/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall
|
Precision Test (Piping)
|
Pass
|
1/9/2023
|
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
7/1/2026
|
Tank Number 6
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
10/20/1988 |
|
Abandoned Material: |
|
| Current Age: |
40 |
|
Abandoned Date: |
|
| Install Date: |
3/17/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
7/21/2025 |
7/21/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
7/1/2026 |
7/1/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
7/1/2026 |
7/1/2027 |
|
Overfill Prev Device
|
Ball Only Removed Ball Float Vent Valve |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/21/2025 |
7/21/2028 |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated |
7/21/2025 |
7/21/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
7/21/2025 |
7/21/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall
|
Precision Test (Piping)
|
Pass
|
1/9/2023
|
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
7/1/2026
|
Tank Number 7
| Capacity: |
550 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
12/20/1995 |
|
OSFM
First Notify Date: |
4/15/1991 |
|
Abandoned Material: |
|
| Current Age: |
9 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found