Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0025647 |
The Kottayam Corporation |
Current Owner |
12/15/1995 |
| U0037257 |
PM 1315 Incorporated |
Former Owner |
6/1/2012 |
| U0025647 |
The Kottayam Corporation |
Former Owner |
12/15/1995 |
| U0010471 |
ExxonMobil Oil Corporation |
Former Owner |
12/31/1967 |
Notice of Violations (Current)
No Notice of Violations Found
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 03-0908 |
6/19/2003 |
Removal Log |
02612-2003REM |
| 2022-0343 |
5/17/2022 |
Removal Log |
00439-2022REM |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 95-2200 |
Eligible |
1/31/2002
|
2/22/2002
|
$10,000
|
|
| 03-0908 |
Eligible |
10/9/2003
|
10/21/2003
|
$10,000
|
|
| 20220343 |
Eligible |
7/1/2022
|
7/6/2022
|
$5,000
|
Letter
|
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/1/1988 |
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
19 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1969 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/1/1988 |
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
19 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1969 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/1/1988 |
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
19 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1969 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
550 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/1/1988 |
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
19 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1969 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/17/2022 |
|
OSFM
First Notify Date: |
12/19/1988 |
|
Abandoned Material: |
|
| Current Age: |
33 |
|
Abandoned Date: |
|
| Install Date: |
10/1/1988 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/31/2020 |
|
Fee Due: |
$0.00 |
| Product Date: |
10/1/1988 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
11/13/2015 |
11/13/2018 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/7/2017 |
6/7/2018 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve |
No passing test found |
No passing test found |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping Ameron |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/17/2022 |
|
OSFM
First Notify Date: |
12/19/1988 |
|
Abandoned Material: |
|
| Current Age: |
33 |
|
Abandoned Date: |
|
| Install Date: |
10/1/1988 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/31/2020 |
|
Fee Due: |
$0.00 |
| Product Date: |
10/1/1988 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
11/13/2015 |
11/13/2018 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/7/2017 |
6/7/2018 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve |
No passing test found |
No passing test found |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping Ameron |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 7
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/17/2022 |
|
OSFM
First Notify Date: |
12/19/1988 |
|
Abandoned Material: |
|
| Current Age: |
33 |
|
Abandoned Date: |
|
| Install Date: |
10/1/1988 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/31/2020 |
|
Fee Due: |
$0.00 |
| Product Date: |
10/1/1988 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
11/13/2015 |
11/13/2018 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/7/2017 |
6/7/2018 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve |
No passing test found |
No passing test found |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping Ameron |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 8
| Capacity: |
1000 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
6/19/2003 |
|
OSFM
First Notify Date: |
12/19/1988 |
|
Abandoned Material: |
|
| Current Age: |
14 |
|
Abandoned Date: |
|
| Install Date: |
10/1/1988 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
10/1/1988 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found