Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2009009
Status: Active
Facility Name: 76 Icon Legacy Group
Address: 1401 River Oaks Drive Calumet City, IL 60409
County: Cook
Property Parcel: 29-24-200-005-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001286
Green Tag Issue Date: 4/30/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Peak Point Petro Group Inc.
Owner Address: 1401 River Oaks Drive Calumet City, IL 60409
Owner Status: Current Owner
Purchase Date: 5/9/2025
Type of Financial Responsibility:
Financial Responsibility Reporting Due Date:

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041748 Peak Point Petro Group Inc. Current Owner 5/9/2025
U0034093 Esquire Petroleum, LLC Former Owner 2/14/2007
U0010471 ExxonMobil Oil Corporation Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00312-2026CAT Cathodic Protection Approved / Issued 3/23/2026 3/23/2026 9/23/2026 Documents
01699-2025UPG Upgrade Approved / Issued 12/31/2025 12/31/2025 6/30/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020260327 (Pending)    Issue Date: 2/9/2026    Expiration Date: 4/10/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h)

NOV Number: E0020260328 (Pending)    Issue Date: 2/9/2026    Expiration Date: 4/10/2026    View NOV Form

Tanks Violations
Facility Financial responsibility must be reported yearly - The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. (Submit this form after the change of ownership notification form has been approved.)
Facility Missing copies of 30 day Walkthrough Inspection Report. - Missing 30 day walk throughs. Only have 2026.
4 Open electrical conduit or junction boxes. - Junction box in Diesel STP is missing a plug in the junction box leaving the junction box open. Replace plug.
1, 2, 3, 4 Required monthly tank leak test records not available. - Maintain one PASSING report per TANK, per month, from ATG. Reference 175.630 c)2)B)
Facility Submit Notification Form For Ownership Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. Select “New Owner” as the type of notification form. ( Make sure you write down the access Code that is given to you when you start the notification form.) Owner has to match as it appears on the deed.
1, 2, 3, 4 Tank precision test required. - Due to missing monthly tank tapes.
1 Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Clamp on Cathodic protection is broke off pipe. Repair/replace and retest.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
97-2404 Eligible 11/8/2001 11/15/2001 $10,000
06-1452 Eligible 6/5/2007 7/2/2007 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Regular Currently in use Federal $0.00
3 10000 Gasoline - Premium Currently in use Federal $0.00
4 10000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms