Notice of Violatlions (Current)
NOV Number:
E0020260805
(Pending)
Issue Date:
3/26/2026
Expiration Date:
5/25/2026
View NOV Form
| Tanks |
Violations |
| 9 |
Install or replace lockable fill pipe caps. - Snap cap broke. Repair/replace. |
| 6, 7, 8 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Will need to see documentation that containment was fixed and tested. |