Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2007770
Status: Active
Facility Name: Blue Island CO
Address: 2427 Union Street Blue Island, IL 60406
County: Cook
Property Parcel:
Facility Type: Utility
Owner Type: Private
Green Tag Decal: Z001326
Green Tag Issue Date: 8/20/2024
Green Tag Expire Date: 12/31/2026
MFD Type: N/A

Owner Details

Owner Name: AT&T Corp.
Owner Address: 311 S. Akard Street, Room 12 Dallas, TX 75202
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 6/4/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0034340 AT&T Corp. Current Owner
U0007227 Ameritech d/b/a AT&T Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261079 (Pending)    Issue Date: 4/22/2026    Expiration Date: 6/21/2026    View NOV Form

Tanks Violations
2 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Last tested 2/21/2023.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/2/1986 Abandoned Material:
Current Age: 48 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 11/30/1990 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 2500 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/14/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 12/10/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping American with Sensors/No Test Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 2/2/2026 2/2/2027
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 4/10/2026 4/10/2027
Overfill Prev Device Overfill Alarm 2/2/2026 2/2/2029
Piping Fiberglass Chase N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 5/5/2026 5/5/2029
Leak Detect - Piping Sump Sensor 2/2/2026 2/2/2027
Spill Contain Device Single Wall Spill Bucket 2/2/2026 2/2/2029
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 2/26/2020
Leak Detect - Piping American with Sensors/No Test Suction Functional Pass 2/20/2024

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found