Notice of Violatlions (Current)
NOV Number:
E0020260646
(Pending)
Issue Date:
3/12/2026
Expiration Date:
5/11/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
NOV Number:
E0020260647
(Pending)
Issue Date:
3/12/2026
Expiration Date:
5/11/2026
View NOV Form
| Tanks |
Violations |
| 9 |
Line interstitial sensors have been raised and rendered inoperational. - 175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump. |
| 5, 6, 7, 8, 9 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall
be maintained in a dry, clean state. |