Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2007053
Status: Active
Facility Name: Circle K #6864
Address: 5500 S. Pulaski Chicago, IL 60629
County: Cook
Property Parcel: 19-15-207-021-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z002267
Green Tag Issue Date: 5/8/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: RDK Ventures LLC
Owner Address: 1120 W. Warner Rd. Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures LLC Current Owner 1/7/2010
U0027449 Equilon Enterprises, LLC Former Owner 1/1/1978
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260921 (Pending)    Issue Date: 4/6/2026    Expiration Date: 6/5/2026    View NOV Form

Tanks Violations
4, 5 Not Vented Properly
4, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4 Stick inserted in drop tube overfill device rendering it inoperative - Remove stick.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
19-0244 3/12/2019 Removal Log 00233-2019REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
88-0192 Eligible 9/29/2011 11/23/2011 $50,000
20190244 Eligible 5/6/2019 5/14/2019 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/12/2019
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 1/1/1978 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1978

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 2/5/2013 2/5/2018
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/16/2019 1/16/2020
Leak Detect - Piping Sump Sensor 1/16/2019 1/16/2020
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/16/2019 1/16/2020
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/12/2019
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 1/1/1978 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1978

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 2/5/2013 2/5/2018
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/16/2019 1/16/2020
Leak Detect - Piping Sump Sensor 1/16/2019 1/16/2020
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/16/2019 1/16/2020
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/12/2019
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 1/1/1978 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1978

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 2/5/2013 2/5/2018
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/16/2019 1/16/2020
Leak Detect - Piping Sump Sensor 1/16/2019 1/16/2020
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 1/16/2019 1/16/2020
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/24/2019 Abandoned Material:
Current Age: 7 Abandoned Date:
Install Date: 3/20/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/16/2019

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/5/2025 12/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/5/2025 12/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/5/2025 12/5/2026
Overfill Prev Device Overfill Drop Tube Valve 1/31/2025 1/31/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/24/2024 7/24/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/5/2025 12/5/2026
Spill Contain Device Double Wall Spill Bucket 1/15/2024 1/15/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/5/2025



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/24/2019 Abandoned Material:
Current Age: 7 Abandoned Date:
Install Date: 3/20/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/16/2019

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/5/2025 12/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/5/2025 12/5/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/5/2025 12/5/2026
Overfill Prev Device Overfill Drop Tube Valve 12/30/2024 12/30/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/24/2024 7/24/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/5/2025 12/5/2026
Spill Contain Device Double Wall Spill Bucket 1/15/2024 1/15/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/5/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/24/2024 7/24/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/5/2025 12/5/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/24/2024 7/24/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/5/2025 12/5/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/24/2024 7/24/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/5/2025 12/5/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/24/2024 7/24/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/5/2025 12/5/2026

MFD Motorfuel Dispensing Forms

No Forms Found