Notice of Violatlions (Current)
NOV Number:
E0020260531
(Pending)
Issue Date:
3/3/2026
Expiration Date:
5/2/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
NOV Number:
E0020260532
(Pending)
Issue Date:
3/3/2026
Expiration Date:
5/2/2026
View NOV Form
| Tanks |
Violations |
| 4, 5, 6 |
Line interstitial sensors have been raised and rendered inoperational. - Regular STP, Dispensers 1/2 and 5/6 |
| 4, 5, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 4, 5, 6 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - All STPs and dispenser 1/2 |