Notice of Violatlions (Current)
NOV Number:
E0020252503
(Pending)
Issue Date:
9/23/2025
Expiration Date:
11/22/2025
View NOV Form
| Tanks |
Violations |
| Facility |
LP gas storage lacks proper collision protection or a 40" measurement from cabinet to a 5" raised sidewalk - Need to move the parking blocks to where they are 40" inches infront of the the Cabinet. |
NOV Number:
E0020252504
(Pending)
Issue Date:
9/23/2025
Expiration Date:
11/22/2025
View NOV Form
| Tanks |
Violations |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete. |
| Facility |
Financial responsibility must be reported yearly - Financial Responsibility form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
| Facility |
Miscellaneous - Outside Emergency stop not marked.
Each emergency stop shall be identified by an approved sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. Reference 175.210 d)3) |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough shall be performed by a licensed contractor shall be conducted and documentation maintained on site. |
| Facility |
Missing copy of emergency instructions or emergency procedures plan - Need to fill out completely. |
| 5, 6, 7 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form. |
| 5, 6, 7 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Nov's are not due until 11/22/2025 |
NOV Number:
E0020253010
(Pending)
Issue Date:
11/12/2025
Expiration Date:
1/11/2026
View NOV Form
| Tanks |
Violations |
| 5, 7 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Regular and Diesel STPs. We will need documentation of STPs being fixed. |