Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2006920
Status: Active
Facility Name: Hickory Hills Food Mart
Address: 9459 S. Roberts Rd. Hickory Hills, IL 60457
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA00174
Green Tag Issue Date: 3/18/2025
Green Tag Expire Date: 12/31/2027
MFD Type: Self Service

Owner Details

Owner Name: Hickory Hills Food Mart
Owner Address: 9459 S. Roberts Road Hickory Hills, IL 60457
Owner Status: Current Owner
Purchase Date: 12/28/2010
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 12/13/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036100 Hickory Hills Food Mart Current Owner 12/28/2010
U0027449 Equilon Enterprises, LLC Former Owner 1/1/1970
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00479-2026LIN Lining Inspection Approved / Issued 4/28/2026 4/29/2026 10/29/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020260768 (Pending)    Issue Date: 3/18/2026    Expiration Date: 6/12/2026    View NOV Form

Tanks Violations
1, 2, 3 Annual electronic line leak detector test not completed. - Last tested on 2-19-2025
1, 2, 3 Annual leak detection certification not completed (Required annually). - Last tested on 2-19-2025
3 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Please replace street plate cover and support over the E-85 STP
Facility Financial responsibility must be reported yearly - https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility
1, 2, 3 Tank internal lining inspection past due (Required every 5 years). - Last test was 3-4-2021

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-0360 Eligible 5/20/2003 6/19/2003 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 48 Abandoned Date:
Install Date: 1/1/1978 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 5/30/2023 5/30/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal Bridgeport Chemical Glass Armor GA 27P 3/4/2021 3/4/2026
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/19/2025 2/19/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/19/2025 2/19/2026
Overfill Prev Device Overfill Drop Tube Valve 8/31/2023 8/31/2026
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Double Wall Spill Bucket 8/31/2023 8/31/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 2/19/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 3/5/2021



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 48 Abandoned Date:
Install Date: 1/1/1978 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 5/30/2023 5/30/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal Bridgeport Chemical Glass Armor GA 27P 3/4/2021 3/4/2026
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/19/2025 2/19/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/19/2025 2/19/2026
Overfill Prev Device Overfill Drop Tube Valve 8/31/2023 8/31/2026
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Double Wall Spill Bucket 8/31/2023 8/31/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 2/19/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 8/31/2023



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 56 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1970

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 5/30/2023 5/30/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal Bridgeport Chemical Glass Armor GA 27P 3/4/2021 3/4/2026
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/19/2025 2/19/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 2/19/2025 2/19/2026
Overfill Prev Device Overfill Drop Tube Valve 8/31/2023 8/31/2026
Piping Fiberglass Single Wall Piping A.O. Smith N/A N/A
Piping Single Wall STP/Tanktop Sump 8/31/2023 8/31/2026
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Double Wall Spill Bucket 8/31/2023 8/31/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping A.O. Smith Precision Test (Piping) Pass 2/19/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 3/5/2021

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/19/2025 2/19/2028
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/19/2025 2/19/2028
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/31/2023 8/31/2026
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/19/2025 2/19/2028
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms