Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0041578 |
15901 Real Estate, Inc. |
Current Owner |
3/13/2025 |
| U0027449 |
Equilon Enterprises, LLC |
Former Owner |
7/1/1983 |
| U0013849 |
Shell Oil Products |
Former Owner |
12/31/1967 |
| U0036385 |
Harvey Petroleum, Inc. |
Former Owner |
|
| U0031151 |
Shell Oil Products US c/o Gilbarco Veeder-Root |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020261558
(Pending)
Issue Date:
6/16/2026
Expiration Date:
8/15/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3, 4 |
Line interstitial sensors have been raised and rendered inoperational. - Repair/replace sensor(s) into proper location so that it can function as designed. (All Dispensers and STPS) Needs to be touching the bottom of the containment. |
| Facility |
Miscellaneous |
| 1, 2, 3, 4 |
Piping interstitial must be open in all sumps - (All Dispensers)
Product piping test boots shall be pulled back after testing to allow the interstice to be open to the sump sensors 175.420 b) (Or Shrader valves need to be removed) |
| 1, 2, 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 2 |
Verify and test piping sump sensor for positive shutdown - L8 Regular East STP Sump sensor is in water and in alarm. Sensor is not shuting product down. Repair/Replace. (According to our records all STP sensors should be programmed for positive shutdown.) |
| 1, 2, 3, 4 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Will need to see documentation that the containments are fixed. (Regular East STP, Premium STP, and Diesel STP. Dispensers 7/8 and 11/12.) |
NOV Number:
E0020261559
(Pending)
Issue Date:
6/16/2026
Expiration Date:
8/15/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
| Facility |
Miscellaneous - Provide appropriate collision protection for LP gas storage cabinet. Refer to OSFM Rules section 175.210 q)1)C) |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 97-0012 |
Eligible |
3/27/1998
|
4/9/1998
|
$10,000
|
|
| 94-0944 |
Returned |
3/11/2002
|
3/25/2002
|
$Not Selected
|
|
| 05-0657 |
Eligible |
12/19/2005
|
1/30/2006
|
$10,000
|
|
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/25/1986 |
|
Abandoned Material: |
|
| Current Age: |
43 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1983 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1983 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
2/14/2026 |
2/14/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD |
2/14/2026 |
2/14/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
3/4/2025 |
3/4/2028 |
|
Piping
|
Fiberglass Double Wall A.O. Smith |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
4/15/2025 |
4/15/2028 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
4/15/2025 |
4/15/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
3/4/2025 |
3/4/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall A.O. Smith
|
Precision Test (Piping)
|
Pass
|
2/14/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
2/19/2025
|
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
7/7/2008
|
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/25/1986 |
|
Abandoned Material: |
|
| Current Age: |
43 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1983 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1983 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
2/14/2026 |
2/14/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD |
2/14/2026 |
2/14/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
3/4/2025 |
3/4/2028 |
|
Piping
|
Fiberglass Double Wall A.O. Smith |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
4/15/2025 |
4/15/2028 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
4/15/2025 |
4/15/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
3/4/2025 |
3/4/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall A.O. Smith
|
Precision Test (Piping)
|
Pass
|
2/14/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
9/20/2022
|
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
7/7/2008
|
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/25/1986 |
|
Abandoned Material: |
|
| Current Age: |
43 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1983 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1983 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
2/14/2026 |
2/14/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD |
2/14/2026 |
2/14/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
3/4/2025 |
3/4/2028 |
|
Piping
|
Fiberglass Double Wall A.O. Smith |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
4/15/2025 |
4/15/2028 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
4/15/2025 |
4/15/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
3/4/2025 |
3/4/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall A.O. Smith
|
Precision Test (Piping)
|
Pass
|
2/14/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
9/20/2022
|
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
7/7/2008
|
Tank Number 4
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/25/1986 |
|
Abandoned Material: |
|
| Current Age: |
43 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1983 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1983 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
2/14/2026 |
2/14/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD |
2/14/2026 |
2/14/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/15/2025 |
4/15/2028 |
|
Piping
|
Fiberglass Double Wall A.O. Smith |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
4/15/2025 |
4/15/2028 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
4/15/2025 |
4/15/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
4/15/2025 |
4/15/2028 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall A.O. Smith
|
Precision Test (Piping)
|
Pass
|
2/14/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
9/20/2022
|
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
7/7/2008
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found