Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2006917
Status: Active
Facility Name: Harvey Shell
Address: 15901 South Dixie Highway Harvey, IL 60426
County: Cook
Property Parcel: 29-19-106-015-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001291
Green Tag Issue Date: 6/4/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: 15901 Real Estate, Inc.
Owner Address: 15901 S. Dixie Highway Harvey, IL 60428
Owner Status: Current Owner
Purchase Date: 3/13/2025
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/21/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041578 15901 Real Estate, Inc. Current Owner 3/13/2025
U0027449 Equilon Enterprises, LLC Former Owner 7/1/1983
U0013849 Shell Oil Products Former Owner 12/31/1967
U0036385 Harvey Petroleum, Inc. Former Owner
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261558 (Pending)    Issue Date: 6/16/2026    Expiration Date: 8/15/2026    View NOV Form

Tanks Violations
1, 2, 3, 4 Line interstitial sensors have been raised and rendered inoperational. - Repair/replace sensor(s) into proper location so that it can function as designed. (All Dispensers and STPS) Needs to be touching the bottom of the containment.
Facility Miscellaneous
1, 2, 3, 4 Piping interstitial must be open in all sumps - (All Dispensers) Product piping test boots shall be pulled back after testing to allow the interstice to be open to the sump sensors 175.420 b) (Or Shrader valves need to be removed)
1, 2, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
2 Verify and test piping sump sensor for positive shutdown - L8 Regular East STP Sump sensor is in water and in alarm. Sensor is not shuting product down. Repair/Replace. (According to our records all STP sensors should be programmed for positive shutdown.)
1, 2, 3, 4 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Will need to see documentation that the containments are fixed. (Regular East STP, Premium STP, and Diesel STP. Dispensers 7/8 and 11/12.)

NOV Number: E0020261559 (Pending)    Issue Date: 6/16/2026    Expiration Date: 8/15/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h)
Facility Miscellaneous - Provide appropriate collision protection for LP gas storage cabinet. Refer to OSFM Rules section 175.210 q)1)C)

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
97-0012 Eligible 3/27/1998 4/9/1998 $10,000
94-0944 Returned 3/11/2002 3/25/2002 $Not Selected
05-0657 Eligible 12/19/2005 1/30/2006 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 43 Abandoned Date:
Install Date: 1/1/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1983

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/14/2026 2/14/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 2/14/2026 2/14/2027
Overfill Prev Device Overfill Drop Tube Valve 3/4/2025 3/4/2028
Piping Fiberglass Double Wall A.O. Smith Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 4/15/2025 4/15/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/15/2025 4/15/2028
Spill Contain Device Single Wall Spill Bucket 3/4/2025 3/4/2028
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 2/14/2026
Tank Fiberglass Single Wall Precision Test (Tank) Pass 2/19/2025
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 7/7/2008



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 43 Abandoned Date:
Install Date: 1/1/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1983

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/14/2026 2/14/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 2/14/2026 2/14/2027
Overfill Prev Device Overfill Drop Tube Valve 3/4/2025 3/4/2028
Piping Fiberglass Double Wall A.O. Smith Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 4/15/2025 4/15/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/15/2025 4/15/2028
Spill Contain Device Single Wall Spill Bucket 3/4/2025 3/4/2028
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 2/14/2026
Tank Fiberglass Single Wall Precision Test (Tank) Pass 9/20/2022
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 7/7/2008



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 43 Abandoned Date:
Install Date: 1/1/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1983

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/14/2026 2/14/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 2/14/2026 2/14/2027
Overfill Prev Device Overfill Drop Tube Valve 3/4/2025 3/4/2028
Piping Fiberglass Double Wall A.O. Smith Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 4/15/2025 4/15/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/15/2025 4/15/2028
Spill Contain Device Single Wall Spill Bucket 3/4/2025 3/4/2028
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 2/14/2026
Tank Fiberglass Single Wall Precision Test (Tank) Pass 9/20/2022
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 7/7/2008



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 43 Abandoned Date:
Install Date: 1/1/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1983

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/14/2026 2/14/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 2/14/2026 2/14/2027
Overfill Prev Device Overfill Drop Tube Valve 4/15/2025 4/15/2028
Piping Fiberglass Double Wall A.O. Smith Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 4/15/2025 4/15/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/15/2025 4/15/2028
Spill Contain Device Double Wall Spill Bucket 4/15/2025 4/15/2028
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test (Piping) Pass 2/14/2026
Tank Fiberglass Single Wall Precision Test (Tank) Pass 9/20/2022
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 7/7/2008

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/15/2025 4/15/2028
Leak Detect - Piping Sump Sensor 2/14/2026 2/14/2027



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/4/2025 3/4/2028
Leak Detect - Piping Sump Sensor 2/14/2026 2/14/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/15/2025 4/15/2028
Leak Detect - Piping Sump Sensor 2/14/2026 2/14/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/4/2025 3/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/14/2026 2/14/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/4/2025 3/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/14/2026 2/14/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/4/2025 3/4/2028
Leak Detect - Piping Sump Sensor 2/14/2026 2/14/2027

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

No Forms Found