Notice of Violatlions (Current)
NOV Number:
E0020251562
(Pending)
Issue Date:
6/23/2025
Expiration Date:
8/22/2025
View NOV Form
Tanks |
Violations |
Facility |
Financial responsibility must be reported yearly - Past Due. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
Facility |
Submit Notification Form For Ownership Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. Select “New Owner” as the type of notification form. |
NOV Number:
E0020251749
(Pending)
Issue Date:
7/10/2025
Expiration Date:
9/8/2025
View NOV Form
Tanks |
Violations |
Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum signage is not up to code. Reference 175.210 o) (Self-Serve Column Warning) |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
NOV Number:
E0020251750
(Pending)
Issue Date:
7/10/2025
Expiration Date:
9/8/2025
View NOV Form
Tanks |
Violations |
Facility |
Facility Operation and Maintenance Plan not completed or available. - Need to fill out completely. |
Facility |
Miscellaneous - Each emergency stop shall be identified by an approved sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. Reference 175.210 d)3) (Inside E-Stop) |
5 |
Miscellaneous - Equipment in disrepair 176.410 |
5 |
Miscellaneous - USTs must be monitored at least every 30 days for releases. Reference 175.630 |
Facility |
Missing copy of emergency instructions or emergency procedures plan - Needs to be filled out completely. |
Facility |
Missing list of designated Class A/B & C Operators - Needs to be filled out. |
5 |
Precision tank test required. - Due to missing monthly passing tank release detection. |
5, 6, 7 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
5, 6, 7 |
Tank monitor does not appear to function properly and requires maintenance. - Green light is not working. |