Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2006750
Status: Active
Facility Name: 1524 Fuel AP
Address: 1524 Chicago Road Chicago Heights, IL 60411
County: Cook
Property Parcel: 32-20-408-041-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001367
Green Tag Issue Date: 12/23/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: AZ SPE, LLC
Owner Address: 12345 S. Keeler Ave. Alsip, IL 60803
Owner Status: Current Owner
Purchase Date: 7/7/2017
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/29/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037844 AZ SPE, LLC Current Owner 7/7/2017
U0032207 Zahdan, Ahmad Former Owner 7/8/2017
U0033214 MPM 1524, LLC Former Owner 8/23/2007
U0027319 Pettice Auto Electric Former Owner 6/15/1998
U0036510 Muaref, Bilal Former Owner
U0035773 Z & A Oil, Inc. Former Owner
U0035002 1524, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260469 (Pending)    Issue Date: 2/25/2026    Expiration Date: 4/26/2026    View NOV Form

Tanks Violations
6 Install or replace lockable fill pipe caps. - Regular snap cap is missing its gasket. Repair/Replace.
6 Line leak detection equipment in alarm or failed test, must repair or replace. - L1 in alarm. (Regular STP)
6 Miscellaneous - Adequate collision protection to protect against physical damage shall be provided for vent piping. 175.440 a)8)
6 Miscellaneous - Remove fuel from Submersible containment.
7 Miscellaneous - Adequate collision protection to protect against physical damage shall be provided for vent piping. 175.440 a)8)
7 Miscellaneous - Equipment in disrepair 176.410
8 Miscellaneous - Adequate collision protection to protect against physical damage shall be provided for vent piping. 175.440 a)8)
8 Miscellaneous - Equipment in disrepair 176.410
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov/content/dam/soi/en/web/sfm/sfmdocuments/documents/30-day-walkthrough-inspection-report.pdf
6, 7, 8 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. (Liquid Status)
7 Open electrical conduit or junction boxes. - Wire nuts on ATG wiring in sump does not comply with electrical Code.
6, 7, 8 Precision tank test required. - Due to monthly missing tapes. (All Tanks)
6, 7, 8 Required monthly tank interstitial sensor records not available. - Maintain one NORMAL report per TANK, per month, from ATG.
6, 7, 8 Required monthly tank leak test records not available. - Maintain one PASSING report per TANK, per month, from ATG. Reference 175.630 c)2)B)
6, 7, 8 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
05-0087 1/24/2006 Removal Log 00825-2005REM
06-0087 1/24/2006 Removal Log 00825-2005REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
05-0901 Eligible 1/30/2006 2/27/2006 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline Removed Federal $0.00 01/24/2006 - REM
2 6000 Gasoline Removed Federal $0.00 01/24/2006 - REM
3 4000 Diesel Fuel Removed Federal $0.00 01/24/2006 - REM
4 1000 Used Oil Removed Federal $0.00 11/24/1998 - REM
5 1000 Heating Oil Removed State $0.00 11/24/1998 - REM
6 15000 Gasoline - Regular Currently in use Federal $0.00
7 6000 Gasoline - Premium Currently in use Federal $0.00
8 8000 E85 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found