Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2005733
Status: Active
Facility Name: Wilmette Gas, Inc.
Address: 1837 Wilmette Avenue Wilmette, IL 60091
County: Cook
Property Parcel: 05-33-400-109-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002121
Green Tag Issue Date: 12/8/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Wilmette Gas, Inc.
Owner Address: 832 E Rand Rd, Unit 16 Mount Prospect, IL 60056
Owner Status: Current Owner
Purchase Date: 4/28/2023
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/1/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/8/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041062 Wilmette Gas, Inc. Current Owner 4/28/2023
U0016483 Wilmette Auto Service, Inc. Former Owner 1/1/1983

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252844 (Pending)    Issue Date: 10/24/2025    Expiration Date: 12/23/2025    View NOV Form

Tanks Violations
Facility Fire Extinguishers - Past due for annual testing - Fire extinguishers require annual testing. Have annual testing performed and tag all fire extinguishers accordingly.
Facility LP gas storage lacks proper collision protection or a 40" measurement from cabinet to a 5" raised sidewalk - Provide appropriate collision protection for LP tank cage. Refer to OSFM Rules section 175.210 q) for proper placement of collision protection.

NOV Number: E0020252845 (Pending)    Issue Date: 10/24/2025    Expiration Date: 12/23/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and 2 years of documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing copy of written UST facility operation & maintenance plan - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
Facility Missing list of designated Class A/B & C Operators - A comprehensive list of Class A / B / C Operator(s) shall be maintained on site and must be current.
8, 9, 10 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth.
8, 9, 10 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.
8 Stick inserted in drop tube overfill device rendering it inoperative - Remove stick. - A tank depth gauge stick is in the drop tube: remove stick to maintain proper operation of drop tube valve.
8 Tank monitor does not appear to function properly and requires maintenance. - ATG in alarm; repair/replace as necessary to secure alarm. SPECIFICALLY T1: OVERFILL ALARM (COULD BE THE STICK IN THE OVERFILL DROP TUBE).
8, 9, 10 Tank precision test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “NORMAL” from ATG.
8, 9 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Submersible sump(s) contain liquid which is corroding the exposed steel. Install approved cathodic protection to prevent further corrosion of related product piping components, or repair/replace sump and make it water tight. NOTE: BY OCT 2028 CP WILL NEED TO BE REMOVED FROM SUMP AND SUMP MUST BE WATER TIGHT.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
98-3063 12/14/1998 Removal Log 3200-98

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
98-3063 Eligible 4/6/1999 4/23/1999 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 4000 Gasoline Removed Federal $0.00 12/14/1998 - REM
2 4000 Gasoline Removed Federal $0.00 12/14/1998 - REM
3 4000 Gasoline Removed Federal $0.00 12/14/1998 - REM
4 4000 Gasoline Removed Federal $0.00 12/14/1998 - REM
5 1000 Heating Oil Removed State $0.00 12/14/1998 - REM
6 250 Heating Oil Does Not Exist State $0.00
7 250 Heating Oil Does Not Exist State $0.00
8 10000 Gasoline - Regular Currently in use Federal $0.00
9 6000 Gasoline - Premium Currently in use Federal $0.00
10 4000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found