Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2005420
Status: Active
Facility Name: Lansing Fire Station #29
Address: 19300 Burnham Ave. Lansing, IL 60438
County: Cook
Property Parcel: 33-06-402-019-0000
Facility Type: Fire Department
Owner Type: Other Local
Green Tag Decal: Y003504
Green Tag Issue Date: 10/31/2023
Green Tag Expiration Date: 7/22/2025

Owner Details

Owner Name: Village of Lansing
Owner Address: 3141 Ridge Road Lansing, IL 60438
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 10/9/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 10/31/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0008906 Village of Lansing Current Owner
U0008903 Lansing Fire Dept Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251341 (Pending)    Issue Date: 5/23/2025    Expiration Date: 7/22/2025    View NOV Form

Tanks Violations
1 Failed to Empty the Tank to 1" or Less - Tank has been out of service since 7/31/2023.
1 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Randall Wright 708-895-7400 (Lieutenant Village of Lansing Fire Department / A/b Operator) stated taht tank 1 has not been used since 7/31/2023)
1 Submit Notification Form For Tank Status Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change.

NOV Number: E0020251342 (Pending)    Issue Date: 5/23/2025    Expiration Date: 7/22/2025    View NOV Form

Tanks Violations
Facility Fire Extinguishers - Minimum 4A:60BC are not present at each island and at an emergency shutoff switch

NOV Number: E0020251343 (Pending)    Issue Date: 5/23/2025    Expiration Date: 7/22/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
2 Annual leak detection certification not completed (Required annually). - ATG Cert.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
2 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
2 Triennial spill prevention equipment testing not completed.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 1000 Gasoline - Regular Condemned Tank Federal 5/23/2025 $0.00
2 1000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1 Active
2 Active

MFD Motorfuel Dispensing Forms

No Forms Found