Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0014207 |
7-Eleven, Inc. |
Current Owner |
1/1/1986 |
| U0017819 |
Southland Corp |
Former Owner |
1/1/1986 |
| U0023040 |
7-Eleven, Inc./DO NOT USE # |
Former Owner |
|
Notice of Violations (Current)
No Notice of Violations Found
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| N/A |
3/20/2018 |
Removal Log |
01151-2017REM |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 91-2518 |
Eligible |
3/14/1995
|
4/3/1995
|
$10,000
|
|
Tank Number 1
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/28/1988 |
|
OSFM
First Notify Date: |
2/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1987 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/28/1988 |
|
OSFM
First Notify Date: |
2/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
40 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1987 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/28/1988 |
|
OSFM
First Notify Date: |
2/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
40 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1987 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
560 |
|
Petroleum Use: |
Consumptive Use on Premises for Heating |
| Product: |
Heating Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
State |
|
Removed Date: |
4/28/1988 |
|
OSFM
First Notify Date: |
2/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
40 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1987 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
560 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
4/28/1988 |
|
OSFM
First Notify Date: |
2/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
40 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1987 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
3/20/2018 |
|
OSFM
First Notify Date: |
12/14/1993 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
10/20/1992 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
10/22/1992 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Jacketed Steel Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
3/7/2017 |
3/7/2018 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
3/7/2017 |
3/7/2018 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Jacketed Steel Double Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 7
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
3/20/2018 |
|
OSFM
First Notify Date: |
12/14/1993 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
10/20/1992 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
10/22/1992 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Jacketed Steel Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
3/7/2017 |
3/7/2018 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
3/7/2017 |
3/7/2018 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Jacketed Steel Double Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 8
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
3/20/2018 |
|
OSFM
First Notify Date: |
12/14/1994 |
|
Abandoned Material: |
|
| Current Age: |
25 |
|
Abandoned Date: |
|
| Install Date: |
10/20/1992 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
10/22/1992 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Jacketed Steel Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
3/7/2017 |
3/7/2018 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD |
No passing test found |
No passing test found |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
3/7/2017 |
3/7/2018 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Jacketed Steel Double Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 9
| Capacity: |
20000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/8/2018 |
|
Abandoned Material: |
|
| Current Age: |
8 |
|
Abandoned Date: |
|
| Install Date: |
3/27/2018 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/7/2018 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
1/14/2026 |
1/14/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
1/14/2026 |
1/14/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
1/14/2026 |
1/14/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
2/20/2024 |
2/20/2027 |
|
Piping
|
Fiberglass Double Wall NOV Fiberglass Systems Red Thread IIA fiberglass piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
2/19/2024 |
2/19/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
2/19/2024 |
2/19/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
2/20/2024 |
2/20/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 10
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/8/2018 |
|
Abandoned Material: |
|
| Current Age: |
8 |
|
Abandoned Date: |
|
| Install Date: |
3/27/2018 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/7/2018 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
1/14/2026 |
1/14/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
1/14/2026 |
1/14/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
1/14/2026 |
1/14/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
2/20/2024 |
2/20/2027 |
|
Piping
|
Fiberglass Double Wall NOV Fiberglass Systems Red Thread IIA fiberglass piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
2/19/2024 |
2/19/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
2/19/2024 |
2/19/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
2/20/2024 |
2/20/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 11
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/8/2018 |
|
Abandoned Material: |
|
| Current Age: |
8 |
|
Abandoned Date: |
|
| Install Date: |
3/27/2018 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/7/2018 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
1/14/2026 |
1/14/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
1/14/2026 |
1/14/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
1/14/2026 |
1/14/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
2/20/2024 |
2/20/2027 |
|
Piping
|
Fiberglass Double Wall NOV Fiberglass Systems Red Thread IIA fiberglass piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
2/19/2024 |
2/19/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
2/19/2024 |
2/19/2027 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
2/20/2024 |
2/20/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
2/19/2024
|
2/19/2027
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
1/14/2026
|
1/14/2027
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
2/19/2024
|
2/19/2027
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
1/14/2026
|
1/14/2027
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
2/19/2024
|
2/19/2027
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
1/14/2026
|
1/14/2027
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
2/19/2024
|
2/19/2027
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
1/14/2026
|
1/14/2027
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found