Notice of Violations (Current)
NOV Number:
E0020250500
(Formal)
Issue Date:
2/26/2025
Expiration Date:
4/27/2025
View NOV Form
| Tanks |
Violations |
| Facility |
Financial responsibility must be reported yearly - Per 176.220, tank owners/operators must submit an electronic Financial Responsibility Report form on an annual basis. Financial Responsibility must be maintained until the tank is removed or properly abandoned in place by a licensed UST decommissiong contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
| 3 |
Remove single-wall tank(s) - Out of Service greater than 5 Years - The single wall tank was taken out of service on 2/4/20 and is 26 years old. Per 175.810(f), if a UST is not placed back into service within 5 years from the date of last use, the tank system shall be removed within 60 days after the conclusion the 5-year period. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals: https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx |
| 3 |
Submit Notification Form For Tank Status Change - Per 175.810(a)(3), tanks taken out of service are required to notify the OSFM within 30 days of date of last use, on an electronic Notification for Underground Storage Tank form, declaring a tank status change. Tank #3 has been out of service since 2/4/20. Here is the link to the electronic Notification for Underground Storage Tank form, so that you can file that change: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 99-0327 |
2/11/1999 |
Removal Log |
2848-98 |
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
2/11/1999 |
|
OSFM
First Notify Date: |
3/19/1986 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
2/11/1999 |
|
OSFM
First Notify Date: |
3/19/1986 |
|
Abandoned Material: |
|
| Current Age: |
26 |
|
Abandoned Date: |
|
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Condemned Tank |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
3/11/1999 |
|
Abandoned Material: |
|
| Current Age: |
27 |
|
Abandoned Date: |
|
| Install Date: |
2/17/1999 |
|
Red Tag Issue Date: |
2/4/2020 |
| Last Used Date: |
2/4/2020 |
|
Fee Due: |
$0.00 |
| Product Date: |
2/17/1999 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
10/6/2016 |
10/6/2017 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Red Jacket ST 1801 |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found