Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2001699
Status: Active
Facility Name: Evergreen Park Citgo
Address: 2801 W. 87th Street Evergreen Park, IL 60805
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA00306
Green Tag Issue Date: 5/22/2025
Green Tag Expire Date: 12/31/2027
MFD Type: Self Service

Owner Details

Owner Name: Bview Corporation
Owner Address: 2801 W. 87th Street Evergreen Park, IL 60805
Owner Status: Current Owner
Purchase Date: 8/29/2013
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/15/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037374 Bview Corporation Current Owner 8/29/2013
U0031909 A & R Marketers, Inc. Former Owner 9/24/2002
U0030464 Emanuel, Joseph Former Owner 11/1/2001
U0022096 James P Kotsiviras Former Owner 1/4/1993
U0009677 Marek Thomas Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260170 (Pending)    Issue Date: 1/22/2026    Expiration Date: 3/23/2026    View NOV Form

Tanks Violations
6, 7, 8 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
6, 7, 8 Line interstitial sensor functional test not accomplished (Required annually).
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough shall be performed by a licensed contractor shall be conducted and documentation maintained on site.
6, 7, 8 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.
6, 7, 8 Tank interstitial sensor functional test not accomplished (Required annually).

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
16-0962 1/5/2017 Removal Log 01494-2016REM
99-1550 6/25/1999 Removal Log 01982-1999REM
99-1558 6/25/1999 Removal Log 01982-1999REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
20160962 Eligible 2/23/2017 2/23/2017 $5,000 Letter
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8000 Gasoline Removed Federal $0.00 01/05/2017 - REM
2 6000 Gasoline Removed Federal $0.00 01/05/2017 - REM
3 6000 Gasoline Removed Federal $0.00 01/05/2017 - REM
4 500 Used Oil Removed Federal $0.00 06/25/1999 - REM
5 500 Heating Oil Does Not Exist State $0.00
6 12000 Gasoline - Regular Currently in use Federal $0.00
7 4000 Gasoline - Premium Currently in use Federal $0.00
8 4000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found