Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2001001
Status: Active
Facility Name: Central Utility Plant/Northwestern University
Address: 410 E. Huron Street Chicago, IL 60611
County: Cook
Property Parcel: 17-10-201-062-0000
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: Y000488
Green Tag Issue Date: 10/16/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Northwestern University
Owner Address: 2020 Ridge Avenue Evanston, IL 60208
Owner Status: Current Owner
Purchase Date: 1/1/2001
Type of Financial Responsibility: Surety Bond
Financial Responsibility Reporting Due Date: 6/30/2026

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0011147 Northwestern University Current Owner 1/1/2001
U0011147 Northwestern University Former Owner 10/28/1998
U0011149 Northwestern University/DO NOT USE THIS# Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252060 (Pending)    Issue Date: 8/12/2025    Expiration Date: 10/11/2025    View NOV Form

Tanks Violations
6, 7, 8 Annual leak detection certification not completed (Required annually).
Facility Facility Operation and Maintenance Plan not completed or available.
Facility Missing copies of Annual Walkthrough Inspection Report.
6, 7, 8 Submit Notification Form For Tank Status Change - Site is no longer going to operate the UST's, but need to be compliant with testing as long as the tanks are currently in use. Need to complete testing or Place tanks out of service with OSFM notification form and remove product form each tank. Section 175.810 Out of Service a) USTs may be put into an out of service status provided they meet the performance standards for new UST systems or the upgrading requirements specified in 41 Ill. Adm. Code 174, 175 and 176 and 40 CFR 280, except that spill and overfill prevention equipment requirements do not have to be met. The USTs may continue in an out of service status for a period of 5 years from the date of last use provided they meet the following requirements: 1) The tank and product lines shall be emptied immediately upon placing the UST in an out of service status. The UST is empty when all materials have been removed using commonly employed practices so that no more than 2.5 centimeters (one inch) of residue, or 0.3% by weight of the total capacity of the UST system, remain in the system. ] 2) Pursuant to Sections 175.500 and 175.510, all corrosion protection shall be maintained and operational for all tanks and lines, and tested as required, to include flex/pipe connectors. This will include any monthly logs that need to be maintained. 3) OSFM must receive a written request, within 30 days after the date the tank was last used, requesting an out of service status. The request shall be submitted on a Notification for Underground Storage Tanks on OSFM forms (available at https://sfm.illinois.gov/about/divisions/petroleumchemical-safety/applications-and-forms.html).
6, 7, 8 Tank interstitial sensor functional test not accomplished (Required annually).

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
97-1884 5/27/1998 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 1/12/1999
OSFM First Notify Date: 1/22/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/22/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 1/12/1999
OSFM First Notify Date: 1/22/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/22/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 1/12/1999
OSFM First Notify Date: 1/22/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/22/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 1/12/1999
OSFM First Notify Date: 1/22/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/22/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/27/1998
OSFM First Notify Date: 1/22/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 5/27/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 35000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/21/1998 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 10/28/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/29/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 6/20/2024 6/20/2025
Overfill Prev Device Overfill Alarm 12/20/2022 12/20/2025
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 7/29/2022 7/29/2025
Leak Detect - Piping Sump Sensor 6/20/2024 6/20/2025
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/2/2023 10/2/2026
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Composite Double Wall Permatank Precision Test (Tank) Pass 7/23/2020



Tank Number 7

Capacity: 35000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/21/1998 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 10/28/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/29/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 6/20/2024 6/20/2025
Overfill Prev Device Overfill Alarm 12/20/2022 12/20/2025
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 7/29/2022 7/29/2025
Leak Detect - Piping Sump Sensor 6/20/2024 6/20/2025
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/2/2023 10/2/2026
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Composite Double Wall Permatank Precision Test (Tank) Pass 7/23/2020



Tank Number 8

Capacity: 35000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/24/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 2/10/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 2/11/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 6/20/2024 6/20/2025
Overfill Prev Device Overfill Alarm 12/20/2022 12/20/2025
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 7/29/2022 7/29/2025
Leak Detect - Piping Sump Sensor 6/20/2024 6/20/2025
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/2/2023 10/2/2026
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Composite Double Wall Permatank Precision Test (Tank) Pass 7/23/2020

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found