Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0041830 |
Larkin Exxon, LLC |
Current Owner |
9/30/2020 |
| U0035735 |
True North Energy, LLC |
Former Owner |
3/8/2010 |
| U0028798 |
Equilon Enterprises, LLC |
Former Owner |
12/1/1998 |
| U0038978 |
KR 2005, Inc. |
Former Owner |
|
| U0031151 |
Shell Oil Products US c/o Gilbarco Veeder-Root |
Former Owner |
|
| U0023652 |
Gas & Grub Inc |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020261401
(Pending)
Issue Date:
5/28/2026
Expiration Date:
7/27/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain most current 2 years on site with other annual testing documentation. ONLY 2 0F 3 ESTOPS TESTED IN 2024 AND 2025. |
| Facility |
Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually, and must be maintained until the tanks are removed or properly abandoned in place by a licensed UST decommissioning contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. ENSURE THAT THE NEW OWNERSHIP CHANGE IS PROCESSED, THEN SUBMIT THE FINANCIAL RESPONSIBILITY. |
| Facility |
Submit Notification Form for Ownership Change - Per 41 Ill. Adm. Code 176.440(g), a change in ownership information must be reported on an electronic Notification for Underground Storage Tank form, within 30 days of the change. This facility had ownership change on 9/30/2020. The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm . |
NOV Number:
E0020261402
(Pending)
Issue Date:
5/28/2026
Expiration Date:
7/27/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 05-1287 |
Eligible |
10/21/2005
|
12/6/2005
|
$10,000
|
|
Tank Number 1
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
1/28/2016 |
|
OSFM
First Notify Date: |
1/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
35 |
|
Abandoned Date: |
|
| Install Date: |
1/23/1981 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
6/1/2011 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Impressed Current Cathodic Protection |
5/19/2011 |
5/19/2012 |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
9/11/2007 |
9/11/2012 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
4/3/2013 |
4/3/2014 |
|
Leak Detect - Piping
|
Sump Sensor |
2/18/2011 |
2/18/2012 |
|
Leak Detect - Piping
|
Stand Alone Sump Sensor |
2/18/2011 |
2/18/2012 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Double Wall Ameron |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
2/18/2011
|
Tank Number 2
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
1/28/2016 |
|
OSFM
First Notify Date: |
1/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
35 |
|
Abandoned Date: |
|
| Install Date: |
1/23/1981 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
6/1/2011 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Impressed Current Cathodic Protection |
5/19/2011 |
5/19/2012 |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
9/11/2007 |
9/11/2012 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
4/3/2013 |
4/3/2014 |
|
Leak Detect - Piping
|
Sump Sensor |
2/18/2011 |
2/18/2012 |
|
Leak Detect - Piping
|
Stand Alone Sump Sensor |
2/18/2011 |
2/18/2012 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Double Wall Ameron |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
2/18/2011
|
Tank Number 3
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
1/28/2016 |
|
OSFM
First Notify Date: |
1/24/1986 |
|
Abandoned Material: |
|
| Current Age: |
31 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1985 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
8/9/2013 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
4/3/2013 |
4/3/2014 |
|
Leak Detect - Piping
|
Sump Sensor |
2/18/2011 |
2/18/2012 |
|
Leak Detect - Piping
|
Stand Alone Sump Sensor |
2/18/2011 |
2/18/2012 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Ball Float Vent Valve |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Double Wall Ameron |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Leak Detect - Piping
|
Non-Discriminating Sump Sensor
|
Sensor Functional
|
Pass
|
2/18/2011
|
Tank Number 4
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/27/2018 |
|
Abandoned Material: |
|
| Current Age: |
7 |
|
Abandoned Date: |
|
| Install Date: |
12/14/2017 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
8/20/2018 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/23/2026 |
6/23/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
6/23/2026 |
6/23/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/23/2026 |
6/23/2029 |
|
Piping
|
Flexible Double Wall OmegaFlex DoubleTrac |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
6/23/2026 |
6/23/2029 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/23/2026 |
6/23/2029 |
|
Piping
|
Ball Valves |
Not applicable |
Not applicable |
|
Piping
|
Shear Valves |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/23/2026 |
6/23/2029 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OmegaFlex DoubleTrac
|
Precision Test (Piping)
|
Pass
|
6/23/2026
|
Tank Number 5
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/27/2018 |
|
Abandoned Material: |
|
| Current Age: |
7 |
|
Abandoned Date: |
|
| Install Date: |
12/14/2017 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
8/20/2018 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/23/2026 |
6/23/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
6/23/2026 |
6/23/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/23/2026 |
6/23/2029 |
|
Piping
|
Flexible Double Wall OmegaFlex DoubleTrac |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
6/23/2026 |
6/23/2029 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/23/2026 |
6/23/2029 |
|
Piping
|
Ball Valves |
Not applicable |
Not applicable |
|
Piping
|
Shear Valves |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/23/2026 |
6/23/2029 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OmegaFlex DoubleTrac
|
Precision Test (Piping)
|
Pass
|
6/23/2026
|
Tank Number 6
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/27/2018 |
|
Abandoned Material: |
|
| Current Age: |
7 |
|
Abandoned Date: |
|
| Install Date: |
12/14/2017 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
8/20/2018 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/23/2026 |
6/23/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
6/23/2026 |
6/23/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/23/2026 |
6/23/2029 |
|
Piping
|
Flexible Double Wall OmegaFlex DoubleTrac |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
6/23/2026 |
6/23/2029 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/23/2026 |
6/23/2029 |
|
Piping
|
Ball Valves |
Not applicable |
Not applicable |
|
Piping
|
Shear Valves |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
6/23/2026 |
6/23/2029 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OmegaFlex DoubleTrac
|
Precision Test (Piping)
|
Pass
|
6/23/2026
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
6/23/2026
|
6/23/2029
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/23/2026
|
6/23/2027
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
6/23/2026
|
6/23/2029
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/23/2026
|
6/23/2027
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
6/23/2026
|
6/23/2029
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/23/2026
|
6/23/2027
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
6/23/2026
|
6/23/2029
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
6/23/2026
|
6/23/2027
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
| Facility Number |
Name |
City |
Received Date |
Letter |
|
2000765
|
Larkin Exxon, LLC
|
Elgin
|
08/15/2018
|
Letter
Form
|