Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2000258
Status: Active
Facility Name: Midlothian Amstar, Inc.
Address: 14506 S. Pulaski Rd. Midlothian, IL 60445
County: Cook
Property Parcel: 28-10-222-034-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002940
Green Tag Issue Date: 1/11/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Midlothian Amstar, Inc.
Owner Address: 14506 S. Pulaski Rd. Midlothian, IL 60445
Owner Status: Current Owner
Purchase Date: 1/16/2004
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/1/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/11/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036847 Midlothian Amstar, Inc. Current Owner 1/16/2004
U0034097 Midlothian Citgo, Inc. Former Owner 1/1/2007
U0029937 Z & S Enterprises Former Owner
U0010278 Wiser Richard & Donna Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251825 (Pending)    Issue Date: 7/18/2025    Expiration Date: 9/16/2025    View NOV Form

Tanks Violations
Facility Fire Extinguishers - Past due for annual testing - Last tested was Nov. 2023

NOV Number: E0020251826 (Pending)    Issue Date: 7/18/2025    Expiration Date: 9/16/2025    View NOV Form

Tanks Violations
1, 2 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
1, 2 Annual leak detection certification not completed (Required annually). - ATG Cert. Past due.
Facility Facility Operation and Maintenance Plan not completed or available. - Go to https://sfm.illinois.gov/content/dam/soi/en/web/sfm/sfmdocuments/documents/oandmtemplate.pdf to download and complete O & M template and maintain completed form on site.
1, 2 Install or replace lockable fill pipe caps. - Snap caps are missing their gaskets. Repair/Replace
1, 2 Line interstitial sensors have been raised and rendered inoperational. - Disp. 5/6 and 7/8.
1, 2 Miscellaneous - Install cathodic protection on all exposed steel on product piping.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov/content/dam/soi/en/web/sfm/sfmdocuments/documents/30-day-walkthrough-inspection-report.pdf
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough shall be performed by a licensed contractor shall be conducted and documentation maintained on site.
Facility Missing list of designated Class A/B & C Operators - Form can be found at https://sfm.illinois.gov to download and complete
1, 2 Monthly line interstitial sensor records not available. - Stand alone sensors are not being montitored monthly. Must keep a log for each dispenser with date inspected, the name of person inspecting, and sensor status, Example: "NORMAL" or "IN ALARM".
1, 2 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1 Shear valve(s) not properly mounted and/or not at proper height. - Shear valve is not mounted properly.
1 Shear valve(s) not properly mounted and/or not at proper height. - Shear valves are to low.
2 Shear valve(s) not properly mounted and/or not at proper height. - Shear valve is not mounted properly.
2 Shear valve(s) not properly mounted and/or not at proper height. - Shear valves are to low.
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2 Triennial spill prevention equipment testing not completed.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/8/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 5/11/1981 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 8/31/2022 8/31/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/24/2025 7/24/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350j with CSLD 7/24/2025 7/24/2026
Overfill Prev Device Overfill Drop Tube Valve 7/24/2025 7/24/2028
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 7/24/2025 7/24/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 7/24/2025
Tank Steel Single Wall Precision Test (Tank) Pass 9/1/2022



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/8/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 5/11/1981 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 8/31/2022 8/31/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/24/2025 7/24/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350j with CSLD 7/24/2025 7/24/2026
Overfill Prev Device Overfill Drop Tube Valve 7/24/2025 7/24/2028
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 7/24/2025 7/24/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 7/24/2025
Tank Steel Single Wall Precision Test (Tank) Pass 9/1/2022

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/29/2023 12/29/2026
Leak Detect - Piping Stand Alone Sump Sensor 7/24/2025 7/24/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/29/2023 12/29/2026
Leak Detect - Piping Stand Alone Sump Sensor 7/24/2025 7/24/2026

MFD Motorfuel Dispensing Forms