1, 2, 3 |
Dispensers - hoses cracked, split or worn and require replacement - Hoses appear to have been compressed. They are not suspended off the ground and their length appears to be causing them to possible be ran over. |
1, 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - Interstitial sensor(s) has/have been raised rendering it/them ineffective. Repair/replace sensor(s) into proper location so that it can function as designed. Sensor is not at the lowest point in the UDC. Liquid in containment. |
Facility |
Missing copies of current testing certificates for operator training |
Facility |
Missing list of designated Class A/B & C Operators |
1, 2, 3 |
Shear valve(s) not in proper working order. - Shear valves appear to be leaking. Bagged at inspection |
1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |