Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1042458
Status: Active
Facility Name: Murphy Oil USA #5398
Address: 3926 W. Riverside Blvd. Rockford, IL 61102
County: Winnebago
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA02045
Green Tag Issue Date: 4/2/2025
Green Tag Expire Date: 12/31/2027
MFD Type: Self Service

Owner Details

Owner Name: Murphy Oil USA, Inc.
Owner Address: 200 E. Peach Street El Dorado, AR 71730
Owner Status: Current Owner / Operator
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/1/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0029289 Murphy Oil USA, Inc. Current Owner / Operator

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260980 (Pending)    Issue Date: 4/13/2026    Expiration Date: 6/12/2026    View NOV Form

Tanks Violations
1, 3 Line leak detection equipment in alarm or failed test, must repair or replace. - Annual third party testing required on all line interstitial sensors. FAILED TEST 3/30/2026
3 Tank interstitial sensors in alarm or failed test, must repair or replace. - Interstitial sensor(s) failed annual testing. Repair/replace as necessary to provide passing test results. FAILED TEST3/30/2026

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/22/2005 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 2/23/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/5/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/30/2026 3/30/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/30/2026 3/30/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 3/30/2026 3/30/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/30/2026 3/30/2027
Overfill Prev Device Overfill Drop Tube Valve 6/17/2024 6/17/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor 3/30/2026 3/30/2027
Piping Single Wall STP/Tanktop Sump 9/21/2023 9/21/2026
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown
Leak Detect - Piping Non-Discriminating Sump Sensor 11/4/2020 11/4/2021
Leak Detect - Piping Non-Discriminating Sump Sensor 9/21/2021 9/21/2022
Leak Detect - Piping Sump Sensor 3/30/2026 3/30/2027
Spill Contain Device Double Wall Spill Bucket 3/30/2026 3/30/2029
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 3/30/2026



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/22/2005 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 2/23/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/5/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/30/2026 3/30/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 3/30/2026 3/30/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/30/2026 3/30/2027
Overfill Prev Device Overfill Drop Tube Valve 8/12/2024 8/12/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor 3/30/2026 3/30/2027
Spill Contain Device Single Wall Spill Bucket 3/30/2026 3/30/2029
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 3/30/2026



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/22/2005 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 2/22/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/5/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/30/2026 3/30/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 3/30/2026 3/30/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/12/2026 5/12/2027
Overfill Prev Device Overfill Drop Tube Valve 8/12/2024 8/12/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor 3/30/2026 3/30/2027
Spill Contain Device Single Wall Spill Bucket 3/30/2026 3/30/2029
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 3/30/2026

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 5/12/2026 5/12/2027



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor 3/30/2026 3/30/2027



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor Beaudreau PL140L / NL qualitative 3/30/2026 3/30/2027



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/21/2023 9/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/30/2026 3/30/2027

MFD Motorfuel Dispensing Forms

No Forms Found