Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1039141
Status: Active
Facility Name: Casey's 5323
Address: 1865 IL Rt. 84 Thomson, IL 61285
County: Carroll
Property Parcel: 12-12-25-200-023; 12-12-25-200-024
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: AA02069
Green Tag Issue Date: 6/23/2025
Green Tag Expire Date: 12/31/2027
MFD Type: Self Service; Unattended Self Service

Owner Details

Owner Name: Casey's Retail Company
Owner Address: 3305 SE Delaware Ave. P.O. Box 3004 Ankeny, IA 50021
Owner Status: Current Owner
Purchase Date: 3/21/2026
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 1/29/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0002560 Casey's Retail Company Current Owner 3/21/2026
U0040956 Holy Angel, LLC Former Owner 5/4/2023
U0038131 A.B.E., Inc. d/b/a The Station Former Owner
U0028915 ABE Enterprises LLC (DBA Atherton Oil) Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260667 (Pending)    Issue Date: 3/12/2026    Expiration Date: 5/11/2026    View NOV Form

Tanks Violations
3, 4 Annual line precision and mechanical line leak detector functional test not completed. - Leak detector(s) failed annual testing. Repair/replace as necessary. Repaired/replaced leak detector(s) shall be retested to show passing results. FAILED TEST 11/5/2025
1, 2 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Triennial testing for qualifying STP piping containment sump(s) failed test. Repair/replace as necessary to pass retesting of sump(s). FAILED TEST 7/11/2025

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/3/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 10/13/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/14/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/5/2025 11/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 2/5/2026 2/5/2027
Overfill Prev Device Overfill Drop Tube Valve 11/5/2025 11/5/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 7/5/2022 7/5/2025
Leak Detect - Piping Sump Sensor 11/5/2025 11/5/2026
Spill Contain Device Single Wall Spill Bucket 11/5/2025 11/5/2028
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 2/5/2026
Tank Fiberglass Single Wall XERXES Precision Test (Tank) Pass 2/5/2026
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 5/11/2010



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/3/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 10/13/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/14/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/5/2025 11/5/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 11/5/2025 11/5/2026
Overfill Prev Device Overfill Drop Tube Valve 11/5/2025 11/5/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 7/5/2022 7/5/2025
Leak Detect - Piping Sump Sensor 11/5/2025 11/5/2026
Spill Contain Device Single Wall Spill Bucket 11/5/2025 11/5/2028
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 2/5/2026
Tank Fiberglass Single Wall XERXES Precision Test (Tank) Pass 2/5/2026
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 5/11/2010



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/3/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 10/13/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/14/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/10/2026 4/10/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 11/5/2025 11/5/2026
Overfill Prev Device Overfill Drop Tube Valve 11/5/2025 11/5/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 7/11/2025 7/11/2028
Leak Detect - Piping Sump Sensor 11/5/2025 11/5/2026
Spill Contain Device Single Wall Spill Bucket 11/5/2025 11/5/2028
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 4/10/2026
Tank Fiberglass Single Wall XERXES Precision Test (Tank) Pass 2/5/2026
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 5/11/2010



Tank Number 4

Capacity: 4000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/3/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 10/13/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/14/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/10/2026 4/10/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 11/5/2025 11/5/2026
Overfill Prev Device Overfill Drop Tube Valve 11/5/2025 11/5/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 7/11/2025 7/11/2028
Leak Detect - Piping Sump Sensor 11/5/2025 11/5/2026
Spill Contain Device Single Wall Spill Bucket 11/5/2025 11/5/2028
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 4/10/2026
Tank Fiberglass Single Wall XERXES Precision Test (Tank) Pass 2/5/2026
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 5/11/2010

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7M

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 8M

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 8S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found