Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1024922
Status: Active
Facility Name: Express Lane Gas & Food Mart Inc. #37
Address: 1320 17th Street Fulton, IL 61252
County: Whiteside
Property Parcel: 01-27-301-006
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000421
Green Tag Issue Date: 7/26/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Arthur J. Johnson Family Limited Partnership
Owner Address: 1305 12th Avenue Rock Falls, IL 61071
Owner Status: Current Owner
Purchase Date: 10/19/2006
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 8/24/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040750 Arthur J. Johnson Family Limited Partnership Current Owner 10/19/2006
U0008040 Johnson Oil Company Former Owner 10/19/2006
U0007007 Horizon Convenience Stores Inc Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261028 (Pending)    Issue Date: 4/16/2026    Expiration Date: 6/15/2026    View NOV Form

Tanks Violations
1, 2, 3 Dispensers - hoses cracked, split or worn and require replacement
Facility Missing copies of 30 day Walkthrough Inspection Report.
1, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 4 Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - STP's

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/26/1989 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 8/19/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/23/2026 4/23/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/23/2026 4/23/2027
Overfill Prev Device Overfill Alarm 3/7/2024 3/7/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/7/2024 3/7/2027
Tank Fiberglass Single Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 4/23/2026



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/26/1989 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 8/19/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/23/2026 4/23/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/23/2026 4/23/2027
Overfill Prev Device Overfill Alarm 3/7/2024 3/7/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/7/2024 3/7/2027
Tank Fiberglass Single Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 4/23/2026



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/26/1989 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 8/19/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/23/2026 4/23/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/23/2026 4/23/2027
Overfill Prev Device Overfill Alarm 3/7/2024 3/7/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/7/2024 3/7/2027
Tank Fiberglass Single Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 4/23/2026



Tank Number 4

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/27/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 7/15/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/15/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/23/2026 4/23/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 4/23/2026 4/23/2027
Overfill Prev Device Overfill Alarm 3/7/2024 3/7/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 4/23/2026 4/23/2029
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/7/2024 3/7/2027
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 4/23/2026

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms