| 6 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP ground cover must be removable to allow for inspection of sump sensor. Containment support deteriorated - repair or replace. |
| 9 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP ground cover deteriorated- repair or replace to allow for inspection of sump sensor. |
| 6, 7, 8 |
Dispensers - hose breakaways are missing or leaking |
| 6, 7, 8 |
Line interstitial sensors have been raised and rendered inoperational. - Disp. 7/8 |
| 5 |
Line leak detection equipment in alarm or failed test, must repair or replace. - DSL Dispenser sump sensor in alarm- L-6 |
| 5 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 6, 7, 8 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Disp. 7/8 |