Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 1022208
Status: Active
Facility Name: Sheetal, Inc. d/b/a F/S Stop
Address: 615 East Lincolnway Morrison, IL 61270
County: Whiteside
Property Parcel: 09-17-330-049
Facility Type: Attended Self-Service/Unattended Self-Service
Owner Type: Private
Green Tag Decal: Z000439
Green Tag Issue Date: 10/7/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service; Unattended Self Service

Owner Details

Owner Name: Sheetal, Inc.
Owner Address: 615 East Lincolnway Morrison, IL 61270
Owner Status: Current Owner
Purchase Date: 8/17/2015
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/1/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038025 Sheetal, Inc. Current Owner 8/17/2015
U0029589 Morrison Fuel 24, L.L.C. Former Owner 8/17/2015
U0029589 Morrison Fuel 24, L.L.C. Former Owner
U0012310 Quint Cities Petroleum Properties Company Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261338 (Pending)    Issue Date: 5/20/2026    Expiration Date: 7/19/2026    View NOV Form

Tanks Violations
Facility Annual Fire Detection Test has not been performed - Last test date 2/10/2025
Facility Signs - Dispensers not marked or labeled with the name of product - Dispenser not marked.

NOV Number: E0020261356 (Pending)    Issue Date: 5/20/2026    Expiration Date: 7/19/2026    View NOV Form

Tanks Violations
6 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP ground cover must be removable to allow for inspection of sump sensor. Containment support deteriorated - repair or replace.
9 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP ground cover deteriorated- repair or replace to allow for inspection of sump sensor.
6, 7, 8 Dispensers - hose breakaways are missing or leaking
6, 7, 8 Line interstitial sensors have been raised and rendered inoperational. - Disp. 7/8
5 Line leak detection equipment in alarm or failed test, must repair or replace. - DSL Dispenser sump sensor in alarm- L-6
5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
6, 7, 8 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Disp. 7/8

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8000 Gasoline Removed Federal $0.00 07/30/1999 - REM
2 8000 Gasoline Removed Federal $0.00 07/30/1999 - REM
3 4000 Gasoline Removed Federal $0.00 07/30/1999 - REM
4 1000 Diesel Fuel Removed Federal $0.00 07/30/1999 - REM
5 11627 Diesel Fuel Currently in use Federal $0.00
6 9696 Gasoline - Regular Currently in use Federal $0.00
7 7796 Gasoline - Mid-grade Currently in use Federal $0.00
8 4431 Gasoline - Premium Currently in use Federal $0.00
9 543 Kerosene Currently in use Federal $0.00

Dispenser Information

Name\ID Status
9 Active
7/8 Active
5/6 Active
3/4 Active
1/2 Active
7S Active
8S Active

MFD Motorfuel Dispensing Forms

No Forms Found