Notice of Violatlions (Current)
NOV Number:
E0020260513
(Pending)
Issue Date:
2/27/2026
Expiration Date:
4/28/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Final inspection for permit 00047-2025CAT resulted in liquid in the UDCs of both dispensers. Cathodic protection must be re-installed or dispensers must be made water tight. Containment testing will be required for any repairs to the structures. Note dispeser 3/4 was tested on 11/26/2024. Verify it is still water tight by repeating the testing. |