Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1011919
Status: Active
Facility Name: Road Ranger #225
Address: 2835 North Main Street Princeton, IL 61356
County: Bureau
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003304
Green Tag Issue Date: 8/21/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Road Ranger, LLC
Owner Address: 1501 Woodfield Rd., Suite 300 S Schaumburg, IL 60173
Owner Status: Current Owner
Purchase Date: 3/11/2003
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/1/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/21/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033990 Road Ranger, LLC Current Owner 3/11/2003
U0023819 Pilot Travel Centers, L.L.C. Former Owner 9/1/2001
U0001282 Beck Oil Company of Illinois Former Owner 12/31/1967
U0017348 First Ranger Petroleum, L.L.C. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251996 (Pending)    Issue Date: 8/7/2025    Expiration Date: 10/6/2025    View NOV Form

Tanks Violations
10, 11, 12, 15, 16, 17, 18 Dispensers - hoses cracked, split or worn and require replacement
10, 11, 12, 15 Line leak detection equipment in alarm or failed test, must repair or replace. - MLLD failed test (T11,T12) or test not performed (T10, T15).
15 Miscellaneous - ATG in alarm
15 Miscellaneous - Check flex connector on regular line at pump 5/6, barrier looks compromised. Phots available.
16 Miscellaneous - ATG in alarm
16 Miscellaneous - Check flex connector on regular line at pump 5/6, barrier looks compromised. Phots available.
10, 11, 12, 15, 16, 17, 18 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
92-0276 2/21/1992 Removal Log
92-0276 2/21/1992 Removal Log 3636-92

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/22/1992
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 2/21/1992
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: 2/21/1992 Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/22/1992
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: 2/21/1992 Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/22/1992
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: 2/21/1992 Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/23/1992
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: 2/21/1992 Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/23/1992
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 1/1/1981 Red Tag Issue Date:
Last Used Date: 2/21/1992 Fee Due: $0.00
Product Date: 1/1/1981

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 1000 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 2/21/1992
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: 2/21/1992 Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 3000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 2/21/1992
OSFM First Notify Date: 2/19/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 9

Capacity: 3000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 2/21/1992
OSFM First Notify Date: 2/19/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1973 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 10

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/16/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 5/1/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/13/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 5/4/2025 5/4/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/2/2024 5/2/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 5/6/2025 5/6/2026
Leak Detect - Tank Other Warren Rogers Assoc. PetroNetwork S3 CITLDS Version D 5/6/2025 5/6/2026
Overfill Prev Device Ball Float Vent Valve 6/4/2024 6/4/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Piping Single Wall Transition Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Double Wall Spill Bucket 5/2/2024 5/2/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/2/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 5/6/2025



Tank Number 11

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/16/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 5/1/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/13/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 5/4/2025 5/4/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/2/2024 5/2/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 5/6/2025 5/6/2026
Leak Detect - Tank Other Warren Rogers Assoc. PetroNetwork S3 CITLDS Version D 5/6/2025 5/6/2026
Overfill Prev Device Ball Float Vent Valve 6/4/2024 6/4/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Piping Single Wall Transition Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/2/2024 5/2/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/5/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 5/6/2025



Tank Number 12

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/16/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 5/1/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/13/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 5/4/2025 5/4/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/2/2024 5/2/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 5/6/2025 5/6/2026
Leak Detect - Tank Other Warren Rogers Assoc. PetroNetwork S3 CITLDS Version D 5/6/2025 5/6/2026
Overfill Prev Device Ball Float Vent Valve 6/4/2024 6/4/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Piping Single Wall Transition Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/2/2024 5/2/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/6/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 5/6/2025



Tank Number 13

Capacity: 20000 Petroleum Use:
Product: 100% Soy Oil (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 6/16/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 5/1/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/14/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Other Warren Rogers Assoc. PetroNetwork S3 CITLDS Version D
Overfill Prev Device Overfill Drop Tube Valve
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 14

Capacity: 4000 Petroleum Use:
Product: Lube Oil CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/16/1992 Abandoned Material: Inert material mixed with portland cement
Current Age: 33 Abandoned Date: 5/19/2015
Install Date: 5/1/1992 Red Tag Issue Date:
Last Used Date: 12/10/2009 Fee Due: $0.00
Product Date: 5/14/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Overfill Prev Device Ball Float Vent Valve EBW 308
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 15

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/24/1998 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 7/14/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/15/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 5/4/2025 5/4/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/2/2024 5/2/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/6/2025 5/6/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 9/11/2024 9/11/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/2/2024 5/2/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/6/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 5/7/2025



Tank Number 16

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/24/1998 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 7/14/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/15/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 5/4/2025 5/4/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/6/2025 5/6/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 9/11/2024 9/11/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/2/2024 5/2/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 5/6/2025
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 2/19/2023
Tank Fiberglass Single Wall Precision Test (Tank) Pass 5/15/2025



Tank Number 17

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/24/1998 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 7/14/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/15/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 5/4/2025 5/4/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/6/2025 5/6/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/6/2025 5/6/2026
Overfill Prev Device Ball Float Vent Valve EBW 308 6/4/2024 6/4/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/2/2024 5/2/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Single Wall STP/Tanktop Sump None Pass 10/15/2018
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/6/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 5/6/2025



Tank Number 18

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/24/1998 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 7/14/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/15/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/6/2025 5/6/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/6/2025 5/6/2026
Overfill Prev Device Overfill Drop Tube Valve 9/11/2024 9/11/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/2/2024 5/2/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/6/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 5/7/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 17

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 17 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 18 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 19

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 19 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 20 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 21

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 21 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 22

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 22 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 23

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 23 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 24

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 24 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 25

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 25 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 26

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 26 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found