Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0036818 |
1010 Cedar Lake, Inc. |
Current Owner |
11/15/2017 |
| U0038448 |
BCB Development XXVII, LLC |
Former Owner |
7/24/2015 |
| U0035603 |
S & P Oil, Inc. |
Former Owner |
9/20/2009 |
| U0033965 |
Schiavone Petroleum, LLC |
Former Owner |
12/28/2006 |
| U0004152 |
DLM Oil Corporation |
Former Owner |
8/1/1988 |
| U0022012 |
Bernies 76 Service |
Former Owner |
12/31/1967 |
Notice of Violations (Current)
NOV Number:
E0020261647
(Pending)
Issue Date:
6/25/2026
Expiration Date:
8/24/2026
View NOV Form
| Tanks |
Violations |
| 6, 7, 8, 9 |
Failed to Empty the Tank to 1" or Less - Tanks must be emptied to <1 inch. |
| 6, 7, 8, 9 |
Submit Notification Form For OOS Tank Status Change - Tanks appear to be out of service. Owner states tenent vacated a month ago and he is looking for a new tenent. He found keys and was able to open the door. There is no power at the facility and the ATG was not functioning. Tanks were red tagged due to an inability to monitor the tanks and the out of service condition. |
NOV Number:
E0020262072
(Pending)
Issue Date:
8/17/2026
Expiration Date:
10/16/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Control station not equipped with an emergency shutoff switch - Control Station was moved and e-stop in no longer located in a readily assesible location. Return contol Staion to its original location or install new e-stop at new control station (this will reqire a new Moter Vehicle Dispense Permit to be filed). Install compliace signage per the regulation.
41 IAC 175.210 d (3):
Equipped with an emergency stop at all control stations, which shall be
conspicuously marked and readily accessible to the attendant, whether or
not the control station is less than 20 feet from any dispenser or a security
booth is provided for the attendant. The emergency stop shall be located
in a position to allow all dispensing devices to be readily visible to the
attendant, or as approved by OSFM. Each emergency stop shall be
identified by a sign on all-weather materials stating "EMERGENCY
STOP" in 2 inch red capital letters. |
| 6, 7, 8 |
Dispensers - hoses cracked, split or worn and require replacement |
| 8 |
Miscellaneous - ATG is in alarm "T4 High Water Warning" Confirmed with tank stick and water finding paste |
| 6, 7, 8, 9 |
Precision line test required. - ATG is unable to run line tests. Perform precision tests on the line. No tests have been done since April 2026. |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 20210690 |
8/20/2021 |
Abandonment Log |
00883-2021ABN |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 20210690 |
Eligible |
9/10/2021
|
9/16/2021
|
$5,000
|
Letter
|
Tank Number 1
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
9/1/1988 |
|
OSFM
First Notify Date: |
5/12/1986 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1964 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
9/1/1988 |
|
OSFM
First Notify Date: |
5/12/1986 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1964 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
9/1/1988 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
9/1/1988 |
|
OSFM
First Notify Date: |
5/12/1986 |
|
Abandoned Material: |
|
| Current Age: |
24 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1964 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
9/1/1988 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
3000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
9/1/1988 |
|
OSFM
First Notify Date: |
5/12/1986 |
|
Abandoned Material: |
|
| Current Age: |
27 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1961 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
9/1/1988 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
2000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Abandoned in place |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/28/1988 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
38 |
|
Abandoned Date: |
8/20/2021 |
| Install Date: |
11/16/1988 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
6/23/2020 |
|
Fee Due: |
$0.00 |
| Product Date: |
11/16/1988 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Isolation Boots Flex Connector |
Not applicable |
Not applicable |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus |
1/30/2021 |
1/30/2022 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
1/15/2021 |
1/15/2024 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/28/1988 |
|
Abandoned Material: |
|
| Current Age: |
38 |
|
Abandoned Date: |
|
| Install Date: |
9/13/1988 |
|
Red Tag Issue Date: |
6/25/2026 |
| Last Used Date: |
6/25/2026 |
|
Fee Due: |
$0.00 |
| Product Date: |
9/13/1988 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
3/19/2026 |
3/19/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus |
3/19/2026 |
3/19/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
1/9/2024 |
1/9/2027 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
1/9/2024 |
1/9/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
8/20/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
7/31/2026
|
Tank Number 7
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/28/1988 |
|
Abandoned Material: |
|
| Current Age: |
38 |
|
Abandoned Date: |
|
| Install Date: |
9/13/1988 |
|
Red Tag Issue Date: |
6/25/2026 |
| Last Used Date: |
6/25/2026 |
|
Fee Due: |
$0.00 |
| Product Date: |
9/13/1988 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
3/19/2026 |
3/19/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus |
3/19/2026 |
3/19/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
1/9/2024 |
1/9/2027 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
1/9/2024 |
1/9/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
8/20/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
7/31/2026
|
Tank Number 8
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/28/1988 |
|
Abandoned Material: |
|
| Current Age: |
38 |
|
Abandoned Date: |
|
| Install Date: |
9/13/1988 |
|
Red Tag Issue Date: |
6/25/2026 |
| Last Used Date: |
6/25/2026 |
|
Fee Due: |
$0.00 |
| Product Date: |
9/13/1988 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
3/19/2026 |
3/19/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus |
3/19/2026 |
3/19/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
1/9/2024 |
1/9/2027 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
1/9/2024 |
1/9/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
12/19/2024
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
7/31/2026
|
Tank Number 9
| Capacity: |
4000 |
|
Petroleum Use: |
Dispensing |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/28/1988 |
|
Abandoned Material: |
|
| Current Age: |
38 |
|
Abandoned Date: |
|
| Install Date: |
11/16/1988 |
|
Red Tag Issue Date: |
6/25/2026 |
| Last Used Date: |
6/25/2026 |
|
Fee Due: |
$0.00 |
| Product Date: |
11/16/1988 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
European with No Test Req Suction |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus |
3/19/2026 |
3/19/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
1/9/2024 |
1/9/2027 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
1/9/2024 |
1/9/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
7/31/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
7/31/2026
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
| Facility Number |
Name |
City |
Received Date |
Letter |
|
1010760
|
Seneca Gulf
|
Seneca
|
10/05/2026
|
Letter
Form
|