Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 1000422
Status: Inactive
Facility Name: Kaney Aviation Properties
Address: 801 Airport Drive Rockford, IL 61109
County: Winnebago
Property Parcel: 15-11-451-005
Facility Type: Airport
Owner Type: Private
Green Tag Decal: BB004380
Green Tag Issue Date: 4/14/2026
Green Tag Expire Date: 12/31/2028
MFD Type: Fleet

Owner Details

Owner Name: Kaney Aviation Properties, LLC
Owner Address: 999 Vanderbilt Beach Road Suite 200 Naples, FL 61109
Owner Status: Current Owner
Purchase Date: 7/1/2005
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/12/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033488 Kaney Aviation Properties, LLC Current Owner 7/1/2005
U0028168 Newell Co Former Owner 6/1/1996
U0024149 Network Air Medical Systems Inc Former Owner 6/1/1994
U0000418 Alpine Aviation Corp Former Owner / Operator 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261311 (Referred to Legal)    Issue Date: 5/19/2026    Expiration Date: 7/18/2026    View NOV Form

Tanks Violations
1 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Single wall tank(s) has/have been out of service for more than one year and must be removed.

NOV Number: E0020262299 (Pending)    Issue Date: 10/1/2026    Expiration Date: 11/30/2026    View NOV Form

Tanks Violations
2 Submit Notification Form For OOS Tank Status Change - Tank 2 is out of service

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Aviation Fuel CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/16/1986 Abandoned Material:
Current Age: 42 Abandoned Date:
Install Date: 1/1/1984 Red Tag Issue Date: 4/14/2026
Last Used Date: 10/25/2024 Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 3/21/2025 3/21/2028
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping European with No Test Req Suction Not applicable Not applicable
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 9/12/2025 9/12/2026
Overfill Prev Device Overfill Drop Tube Valve 9/1/2023 9/1/2026
Piping Steel Single Wall Piping Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 9/18/2020 9/1/2023
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Single Wall Precision Test (Tank) Pass 2/5/2024



Tank Number 2

Capacity: 12000 Petroleum Use: None
Product: Aviation Fuel CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/16/1986 Abandoned Material:
Current Age: 42 Abandoned Date:
Install Date: 1/1/1984 Red Tag Issue Date: 10/1/2026
Last Used Date: 10/1/2026 Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Cathodic Protection 3/21/2025 3/21/2028
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping European with No Test Req Suction Not applicable Not applicable
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 8/26/2026 8/26/2027
Overfill Prev Device Overfill Drop Tube Valve 8/26/2026 8/26/2029
Piping Steel Single Wall Piping Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Double Wall Spill Bucket 8/26/2026 8/26/2029
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Single Wall Precision Test (Tank) Pass 2/5/2024

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump Not applicable Not applicable

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

No Forms Found